Serviceline Industrial Sensors
Serviceline Explosion Protection

Type X and Ex pxb purge and pressurization control unit 6000 Control System

6000 Control System
  • Certified for Class I, Class II, Division I; Zone 1 / Zone 21 to nonhazardous
  • Intrinsically safe electrical/pneumatic manifold assembly
  • Intrinsically safe user interface for programming and monitoring the system
  • Enclosure volume up to 450 ft3 (12.7 m3)
  • Control Unit monitors system operation and controls enclosure power
  • Universal mounting (brackets included)
  • 316L stainless steel Type 4X enclosure

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  6000 Control System

Product Description
6000 Series Type X and Ex pxb purge and pressurization system control unit
General specifications
Operating modemanual, semi-automatic, or fully automatic - programmable
Series6000 Series
SystemType X Purge ; Ex pxb Purge
Number of volume exchanges4 to 19
Hazardous environmentgas, dust, gas and dust
Supply
Rated voltage90 ... 264 V AC, 48 ... 62 Hz / 0.2 A
20 ... 30 V DC
Electrical specifications
ConnectionTerminal blocks
Input
Input IInputs 1, 2, 3, 4: contact input, 5 VDC @ 2 mA
Input typeintrinsically safe
Input IITemperature inputs
Input typeintrinsically safe
Sensor type6000-TEMP
Input IIIEPV-6000 Vent
Input typeintrinsically safe
Input IVUser interface module
ConnectionM8 connector, 4-pin
Input typeintrinsically safe
Output
Output IAUX 1
Output typeDry contacts, SPDT
Inrush current5 A
Contact loading2 A @ 240 VAC resistive load
2 A @ 24 VDC
Output IIAUX 2
Output typeDry contacts, SPDT
Inrush current5 A
Contact loading2 A @ 240 VAC resistive load
2 A @ 24 VDC
Output IIIENC_1, ENC_2 (protected enclosure contacts)
Output typeDry contacts (2) SPST, NO
Contact loading8 A @ 240 VAC / 120 VAC resistive load
8 A @ 24 VDC
Indicators/settings
LED indicationSafe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirement20 ... 120 psig (1.4 ... 8.3 bar) (138 ... 827 kPa) regulated
Safe pressureGas: 0.25" wc (6.4 mm wc) (0.625 mbar) (62 Pa)
Dust: 0.65" wc (16.5 mm wc) (1.6 mbar) (162 Pa)
Gas and Dust: 0.65" wc (16.5 mm wc) (1.6 mbar) ( 162 Pa)
Purge flow rateMaximum flow rate measurement for enclosure size (enclosure volume:flow rate):
< 20 ft3 (0.57 m3): 5, 12 SCFM (141, 340 l/min), or dynamic
20 ... 30 ft3 (0.57 ... 0.85 m3): 5, 12, 20 SCFM (141, 340, 565 l/min), or dynamic
> 30 ft3 (0.85 m3): 5, 12, 20, 30 SCFM (141, 340, 565, 850 l/min), or dynamic
Purge flow and enclosure pressure rateWith EPV-6000-xx-01, EPV-6000-xx-02
5 SCFM @ 1.5" wc, (141 l/min @ 3.7 mbar)
12 SCFM @ 2.0" wc, (340 l/min @ 5.0 mbar)
20 SCFM @ 2.7" wc, (565 l/min @ 6.7 mbar)
30 SCFM @ 4.1" wc, (850 l/min @ 10.2 mbar)

With EPV-6000-xx-03, EPV-6000-xx-04
5 SCFM @ 2.1" wc, (141 l/min @ 5.2 mbar)
12 SCFM @ 2.6" wc, (340 l/min @ 6.5 mbar)
20 SCFM @ 4.1" wc, (565 l/min @ 10.2 mbar)
30 SCFM @ 5.3" wc, (850 l/min @ 13.2 mbar)

With EPV-6000-xx-05, 06
5 SCFM @ 1.8" wc, (141 l/min @ 4.5 mbar)
12 SCFM @ 2.9" wc, (340 l/min @ 7.3 mbar)
20 SCFM @ 7.4" wc, (565 l/min @ 18.5 mbar)
Flow rate for leakage compensationDepends on enclosure seal.

With EPV-6000-xx-01, EPV-6000-xx-02
0.35 SCFM @ 0.25" wc (10.0 l/min @ 6.3 mbar)
1.0 SCFM @ 0.75" wc (28.0 l/min @ 1.9 mbar)

With EPV-6000-xx-03, EPV-6000-xx-04
0.22 SCFM @ 0.25" wc (6.2 l/min @ 6.3 mbar)
0.58 SCFM @ 0.75" wc (16.4 l/min @ 1.9 mbar)

With EPV-6000-xx-05, EPV-6000-xx-06
0.15 SCFM @ 0.25" wc (4.2 l/min @ 6.3 mbar)
0.35 SCFM @ 0.75" wc (10.0 l/min @ 1.9 mbar)
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-30 ... 80 °C (-22 ... 176 °F)
Relative humidity5 ... 95 %, noncondensing
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Connection typePneumatic :
Inlet fitting to manifold: 3/8" ferrule fitting
Outlet fitting from manifold: 3/8" ferrule fitting
Inlet fitting to enclosure: 3/8" bulkhead fitting
Cable gland4 - M16 x 1.5 cable gland
Degree of protectionType 4X , IP66
MaterialEnclosure: 316L (UNS S31603) stainless steel
Manifold valve: anodized 6082 aluminum
Fittings: 316L (UNS S31603) stainless steel
Mass-WH- 11.4 kg (25 lb)
-CK- 7.2 kg (16 lb)
Dimensions183 x 367.5 x 152.5 mm (7.20 x 14.45 x 6.00 inch)
Height367.5 mm
Width183 mm
Depth152.5 mm
Data for application in connection with hazardous areas
EU-type examination certificate
Marking6000 main control unit with housing
6000-xx-S2-UN-xx-xx:
ATEX UL/Demko 07 ATEX 0705753X
II 2 G Ex db ib [ib Gb] [pxb Gb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
II 2 D Ex ib tb [ib Db] [pxb Db] IIIC T60°C Db (-20 °C ≤ Ta ≤ 50 °C)

6000 main control unit kit version
6000-xx-S2-UN-CK-xx:
ATEX UL/Demko 07 ATEX 0705753X
II 2 G Ex db [ib Gb] [pxb Gb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
II 2 D Ex tb [ib Db] [pxb Db] IIIC T80°C Db (-20 °C ≤ Ta ≤ 60 °C)

User interface
6000-UIC-xx:
ATEX UL/Demko 07 ATEX 0705753X
II 2 G Ex ib [pxb Gb] IIC T4 Gb
Directive conformity
Directive 2014/34/EUIEC/EN 60079-0
IEC/EN 60079-1
IEC/EN 60079-2
IEC/EN 60079-11
IEC/EN 60079-31
Directive 94/9/EC
International approvals
UL approval6000 Main control unit with housing
6000-xx-S2-UN-xx-xx:
cULus
Class I, Division 1, Groups A,B,C,D T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Division 1, Groups E,F,G T4 (-20 °C ≤ Ta ≤ 50 °C)
Class I, Zone 1, Group IIC T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Zone 21, Group IIIC T60 °C (-20 °C ≤ Ta ≤ 50 °C)
[Ex i] Associated Equipment
Ex db ib [ib Gb] [pxb Gb] IIC T4 (-20 °C ≤ Ta ≤ 60 °C)
Ex ib tb [ib Db] [pxb Db] IIIC T4 (-20 °C ≤ Ta ≤ 50 °C)
6000 Main control unit kit version
6000-xx-S2-UN-CK-xx:
cULus
Class I, Division 1, Groups A,B,C,D T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Division 1, Groups E,F,G T4 (-20 °C ≤ Ta ≤ 60 °C)
Class I, Zone 1, Group IIC T4
Class II, Zone 21, Group IIIC T60 °C
[Ex i] Associated Equipment
Ex db [ib Gb] [pxb Gb] IIC T4 X (-20 °C ≤ Ta ≤ 60 °C)
Ex tb [ib Db] [pxb Db] IIIC T4 X (-20 °C ≤ Ta ≤ 60 °C) User interface 6000-UIC-xx: cULus (-20 °C ≤ Ta ≤ 60 °C) Class I, Division 1, Groups A,B,C,D T4 Class I, Zone 1, Group IIC T4 Ex i Intrinsically safe
IECEx approval6000 Main Control unit with housing
6000-xx-S2-UN-xx-xx:
IECEx UL 08.0003X
Ex db ib [ib Gb] [pxb Gb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
Ex ib tb [ib Db] [pxb Db] IIIC T60 °C Db (-20 °C ≤ Ta ≤ 50 °C)
6000 Main control unit kit version
6000-xx-S2-UN-CK-xx:
IECEx UL 08.0003X
Ex db [ib Gb] [pxb Gb] IIC T4 Gb (-20 °C ≤ Ta ≤ 60 °C)
Ex tb [ib Db] [pxb Db] IIIC T80 °C Db (-20 °C ≤ Ta ≤ 60 °C) User interface 6000-UIC-xx: IECEx UL 08.0003X Ex ib [pxb Gb] IIC T4 Gb
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027180508
ECLASS 12.027180508
ECLASS 11.027180508
ECLASS 10.0.127180508
ECLASS 9.027180508
ECLASS 8.027180508
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121301

Details: 6000 Control System

Function

The 6000 series consists of the control unit (EPCU)and user interface(UIC) mounted in a 316L stainless steel Type 4X (IP66) enclosure with the pneumatic solenoid valve mounted on the unit. The EPV-6000 relief vent is separate and is mounted to the enclosure.

The user interface allows programming of up to 4 switch inputs, temperature modules, enclosure power contacts, 2 auxiliary outputs, and various operational functions. Also, the user interface screen allows monitoring and easy configuration.

Among the additional features are inputs for system bypass, enclosure power on/off, temperature overload and activation of Rapid Exchange flow for cooling or auxiliary relay for separate cooling source, and delay power shutdown.

Component kits are available for custom installations.

Informative Literature: 6000 Control System

Language Selection:
We are sorry, there are no documents for your language selection. Please select another language.

Product Documentation: 6000 Control System

Language Selection:
Product informationLanguageFile TypeFile Size
Basic Explosion Protection Compendium - Type of Protection "Purge and Pressurization"ENGPDF3860 KB
Brief Instructions
Programming Tree 6000 Series Purge/Pressurization SystemENGPDF1157 KB
Programming Worksheet 6000 Series Purge/Pressurization SystemENGPDF1399 KB
Safety and Security Documentation
Instruction manualENGPDF174 KB
Manuals
Installation and Operation Manual 6000 Series Purge/Pressurization System (USA English)ENGPDF13802 KB

Design / Simulation: 6000 Control System

Language Selection:
CADLanguageFile TypeFile Size
2D / DXF Files for 6000 Series component kit / CAD 2-DALLZIP1162 KB
CAD and STP drawings of 6000 Series complete unit / CAD 2-DALLZIP6729 KB

Approvals: 6000 Control System

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
ATEX CertificateDEMKO 07 ATEX 0705753XALLPDF360 KB
China SITIIAS CCC Ex Certificate2020322304003056 (Katy, TX USA)ALLPDF5433 KB
IECEx Certificate of ConformityIECEx UL 08.0003XALLLINK---
Korea KOSHA14-AV4BO-0083ALLPDF322 KB
PESO (India) CCOEA/P/HQ/MH/104/4757 (P383926)ALLPDF103 KB
UL Hazardous LocationE184741 (RFPW, RFPW7 , RFPZ7)ALLPDF741 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF711 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-B066DALLPDF162 KB

Associated Products: 6000 Control System

Accessories
Termination board for the 6000 Series Purge systempa
EPV-6000 Ventpa

Get to know the smartest way to ensure hazardous location protection and configure your individual purge and pressurization system!