Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Datasheet excerpt: Technical data of
KCD2-R
Product Description |
Sensor output interface terminals with relay output |
Functional safety related parameters |
MTTFd | 19699 a |
Indicators/operating means |
LED yellow | switch output |
Electrical specifications |
Operating voltage | 24 V DC ± 15 % |
Ripple | ≤ 10 % |
Operating current | 16 mA |
Input |
Connection | terminals 2+, 3- |
Connectable sensor types | PNP or NPN 3-wire sensors |
Output |
Switching frequency | ≤ 10 Hz |
Relay | 1 changeover contact |
Contact loading | 30 V DC/2 A resistive load |
Delay | Pull-in: approx. 6 ms Drop-out: approx. 2 ms |
Mechanical life | ≥108 switching cycles |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Noise immunity | EN 61326-1:2013 |
Ambient conditions |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | self-opening apparatus connection terminals, max. core cross-section 0.34 ... 2.5 mm2 |
Mass | 60 g |
Dimensions | 20 mm x 60 mm x 40 mm |
Classifications
System | Classcode |
ECLASS 13.0 | 27210121 |
ECLASS 12.0 | 27210121 |
ECLASS 11.0 | 27210121 |
ECLASS 10.0.1 | 27210121 |
ECLASS 9.0 | 27210121 |
ECLASS 8.0 | 27210121 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC002653 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC002653 |
UNSPSC 12.1 | 41111902 |
Details:
KCD2-R
Design / Simulation:
KCD2-R