Fieldbus power supply for fieldbus power hub |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Connection | Power Rail or terminals 8+, 11+; 9-, 12- | |
Rated voltage | 19.2 ... 35 V DC | |
Rated current | 630 ... 340 mA | |
Power dissipation | typ. 2,0 W | |
Fieldbus connection | ||
Number of segments | 1 | |
Connection | terminals 3+, 6+; 2-, 5-; 1S, 4S (S=screen connection) | |
Rated voltage | 25 ... 28 V | |
Rated current | 360 mA | |
Galvanic isolation | ||
Fieldbus segment/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 250 V AC | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2, ISA S 50.02 part 2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminal , pluggable | |
Core cross section | up to 2.5 mm2 | |
Housing | 20 mm x 115 mm x 107 mm | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 210 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 06 ATEX 553079 X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 | |
International approvals | ||
FM approval | ||
FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X | |
FM marking | AEx/Ex ec IIC T4 | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242611 |
ECLASS 12.0 | 27242611 |
ECLASS 11.0 | 27242611 |
ECLASS 10.0.1 | 27242611 |
ECLASS 9.0 | 27242611 |
ECLASS 8.0 | 27242611 |
ECLASS 5.1 | 27242611 |
ETIM 9.0 | EC002583 |
ETIM 8.0 | EC002583 |
ETIM 7.0 | EC002583 |
ETIM 6.0 | EC002583 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121004 |
This fieldbus power supply is an all-in-one module for single fieldbus segments. It adapts current and voltage and provides the impedance filter required. Reliability of communication is enhanced through galvanic isolation between segment and bulk power supply.
Power output is designed for long cable lengths and device counts suiting the needs of most fieldbus applications. Fieldbus couplers provide explosion protection for live work at the spur where needed.
Availability and a long service life are achieved through a passive impedance filter and a design optimized for low heat dissipation. Modules can be mounted with no spacing required in any direction for an optimized and space-saving cabinet layout. The mobile Advanced Diagnostic Module connects directly to test plug sockets located on the plug-in terminal. In conjunction with the modular Segment Protector it is a perfectly expandable solution.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 55 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
DXF drawing K-Housing, Subject to change without notice / DXF Zeichnung K-Housing, Änderungen vorbehalten | ALL | ZIP | 183 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Canada FM | FM 19 CA 0011X | ALL | 356 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe TUV Nord ATEX II 3 G | TÜV 06 ATEX 553079X | ALL | 2011 KB | |
USA FM | FM 19 US 0015X | ALL | 213 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2718B | ALL | 1039 KB |