Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Surge protector, pluggable module for trunk installation on segment protector |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 1 / Div. 1 | |
Fieldbus connection | ||
Self current consumption | max. 6 mA (for version TCP-LBF-IA1.36.IE.1) , max. 0 mA (for version TCP-LBF-IA1.36.IE.0) | |
Indicators/operating means | ||
LED ERR | green flashing: status OK , red flashing: maintenance required , (for version TCP-LBF-IA1.36.IE.1) | |
Electrical specifications | ||
Rated voltage | 36 V | |
Rated current | 600 mA | |
Voltage protection level | ||
Line/Line | max. 50 V category B2 10/700 µsec , 25 A max. 50 V category C1 8/20 µsec , 300 A max. 55 V category C2 8/20 µsec , 5 kA max. 46 V category C3 1 kV/µsec , 10 A |
|
Line/Earth | max. 1060 V category B2 10/700 µsec , 50 A per line max. 800 V category C1 8/20 µsec , 300 A per line max. 1.5 kV category C2 8/20 µsec , 5 kA per line max. 1.3 kV category C3 1 kV/µsec , 50 A per line max. 1080 V category D1 10/350 µsec , 500 A per line |
|
Screen/Shield indirectly grounded (via GDT) | max. 500 V category B2 10/700 µsec , 100 A max. 600 V category C1 8/20 µsec , 500 A max. 720 V category C2 8/20 µsec , 10 kA max. 550 V category C3 1 kV/µsec , 100 A max. 570 V category D1 10/350 µsec , 1 kA |
|
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Screen/Shield-Earth | max. 100 ns | |
Overstressed fault mode | according IEC 61643-21 line inoperable mode 3 | |
Series resistance in line | 2 Ω +/- 5 % | |
Impulse durability | ||
Per line | 5 kA category C2 8/20 µsec | |
Screen/Shield indirectly grounded (via GDT) | 1 kA category D1 10/350 µsec 10 kA category C2 8/20 µsec |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NAMUR NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | 80 g | |
Grounding | M4 screw and external grounding rail | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | SIRA 12 ATEX 2128X | |
Marking | II 1G Ex ia IIC T4 | |
Voltage | 24 V | |
Current | 500 mA | |
Internal capacitance | 2 nF | |
Internal inductance | 0.1 µH | |
Certificate | SIRA 12 ATEX 4176X | |
Marking | II 3G Ex nAc IIC T4 , II 3G Ex ic IIC T4 | |
Voltage | 33 V | |
Current | 600 mA | |
Internal capacitance | 2 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
Supplementary information | FISCO field device | |
International approvals | ||
CSA approval | CoC 2595441 | |
Control drawing | 116-0365 | |
Approved for | Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 0, Ex ia IIC T4 Class I, Zone 2, Ex ic IIC T4 Class I, Zone 0, AEx ia IIC T4 Class I, Zone 2, AEx ic IIC T4 Class I, Division 2, Groups A, B, C, D T4 Class I, Zone 2, Ex nL IIC T4 Class I, Zone 2, Ex na IIC T4 Class I, Zone 2, AEx nAc IIC T4 |
|
IECEx approval | IECEx SIR 12.0051X | |
Approved for | Ex ia IIC T4 | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
General information | ||
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 19170104 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002584 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121610 |
This fieldbus surge protector is in accordance with IEC 61158-2 and mounts on the trunk connector of FieldConnex ® device couplers, protecting them. It directs power surges to earth via gas discharge tubes. It is certified intrinsically safe for circuits in hazardous areas up to Zone 0/Div. 1 and DART fieldbus. The surge protector is installed in Zone 1 … 2 or Div. 1 … 2.
Integrated diagnostics (option) continuously monitor wear caused by surges. The end of the useful life and thus the need for exchange is indicated in two ways: via an LED and in the control room via the FieldConnex ® Advanced Diagnostics software.
Installation on the trunk connector is without additional wiring even as retrofit.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 227 KB | |
Manuals | |||
Manual Fieldbus Surge Protector, TPH-LBF-IA1.36* , TCP-LBF-IA1.36* , SCP-LBF-IA1.36* | ENG | 6301 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 2-D / CAD 2-D | ALL | ZIP | 454 KB |
CAD 3-D / CAD 3-D | ALL | STP | 5495 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 14.1589 X | ALL | 1153 KB | |
Canada, USA CSA Ex i and Ex n | CSA 13.2595441X | ALL | 114 KB | |
China SITIIAS CCC Ex Certificate | 2020322304003528 (Singapore) | ALL | 1024 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe CSA ATEX Category 1 G | Sira 12 ATEX 2128X | ALL | 215 KB | |
Europe CSA ATEX Category 3 G II 3 G | Sira 12 ATEX 4176X | ALL | 228 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5866 (P506129) | ALL | 100 KB | |
Sira IECEx Certificate of Conformity | IECEx SIR 12.0051X | ALL | LINK | --- |
Control Drawings | ||||
Control drawing CSA / Control drawing CSA | ALL | 92 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-0814CENG | ENG | 1142 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
||||||
Matching System Components | ||||||
|
||||||
|
RSS Info Service for PANOS Updates
Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.