General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Bus or terminals 1-, 2+ | |
Rated voltage | 16.8 ... 31.2 V DC | |
Power dissipation | 0.6 W | |
Power consumption | 1.1 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
NAMUR sensor | ||
Type | 2-wire | |
Connection | terminals 5+, 6 | |
Signal | acc. to EN 60947-5-6 (NAMUR) | |
Sensor supply | 8 V | |
Open-circuit | < 0.1 mA | |
Switching point | 1.2 ... 2.1 mA | |
Short-circuit | > 6 mA | |
Input impedance | 1 kΩ | |
Mechanical contact | ||
Type | 2-wire | |
Connection | terminals 5+, 6 | |
Sensor supply | 15 V | |
External supply | ≤ 32 V | |
Switching point | 8 ... 10 V / 1.2 ... 2.1 mA | |
Frequency | 0 ... 50 Hz , debounce filter | |
Input impedance | 4 kΩ | |
SN sensor | ||
Type | 2-wire | |
Connection | terminals 5+, 6 | |
Sensor supply | 8 V | |
Open-circuit | < 0.1 mA | |
Switching point | 1.2 ... 2.1 mA | |
Short-circuit | > 6 mA | |
Input impedance | 1 kΩ | |
2-wire DC sensor | ||
Type | 2-wire | |
Connection | terminals 5+, 6 | |
Signal | acc. to EN 60947-5-2 | |
Sensor supply | 16 V / 25 mA , short-circuit protected | |
External supply | ≤ 32 V | |
Switching point | 2 ... 5 mA | |
Input impedance | 1 kΩ | |
S0 sensor | ||
Type | 2-wire | |
Connection | terminals 5+, 6 | |
Signal | acc. to EN 62053-31 , Type B | |
Sensor supply | 15 V | |
Switching point | 0.15 ... 2 mA | |
Input impedance | 4 kΩ | |
NPN sensor | ||
Type | 3-wire | |
Connection | terminals 5+, 6, 7- | |
Signal | acc. to EN 60947-5-2 | |
Sensor supply | 16 V / 25 mA , short-circuit protected | |
External supply | ≤ 32 V | |
Switching point | 3 ... 5 V | |
Input impedance | 4 kΩ | |
PNP sensor | ||
Type | 3-wire | |
Connection | terminals 5+, 6, 7- | |
Signal | acc. to EN 60947-5-2 | |
Sensor supply | 16 V / 25 mA , short-circuit protected | |
External supply | ≤ 32 V | |
Switching point | 8 ... 10 V | |
Input impedance | 4 kΩ | |
AC/DC voltage source | ||
Connection | terminals 6, 7- | |
Signal | max. ± 30 V | |
Switching point | 150 ... 400 mV | |
Input impedance | 4 kΩ | |
Function input | ||
Connection | terminal 8 | |
Open loop voltage | 7.5 V | |
Input impedance | approx. 50 kΩ | |
Function 1 | activation start-up override | |
Switching point | < 3 V , edge triggered | |
Adjustment range | 1 ... 6500 s | |
Function 2 | reset restart inhibit | |
Switching point | > 12 V , edge triggered | |
Output | ||
Connection side | control side | |
Connection | terminals 3, 4: | |
Output | signal, relay | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Accuracy | max. 0.1 % of the measurement value | |
Measuring time | ≤ 100 ms | |
Influence of ambient temperature | < 100 ppm/K of the measured value | |
Frequency range | 0.01 ... 50000 Hz | |
Galvanic isolation | ||
Output/power supply | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Input/Other circuits | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP switch | |
Configuration | via DIP switches via software |
|
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | EN 61010-1:2010 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
Mass | approx. 60 g | |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 | |
Height | 97 mm | |
Width | 6.2 mm | |
Depth | 107 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210128 |
ECLASS 12.0 | 27210128 |
ECLASS 11.0 | 27210128 |
ECLASS 10.0.1 | 27210128 |
ECLASS 9.0 | 27210128 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC002918 |
ETIM 8.0 | EC002918 |
ETIM 7.0 | EC002918 |
ETIM 6.0 | EC002918 |
ETIM 5.0 | EC002475 |
UNSPSC 12.1 | 39121007 |
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The device monitors the overspeed condition and the underspeed condition of a digital signal.
The device has an input for the following digital signals:
Mechanical contacts
2-wire sensors (NAMUR, SN, DC, S0)
3-wire sensors (NPN, PNP)
AC/DC voltage sources (magnetic sensors)
custom-specific setting
The input is reverse polarity protected and short-circuit proofed.
The connected sensors can also be supplied externally.
The device compares the input frequency with a user-specified reference frequency. An overspeed condition or an underspeed condition is signaled via the relay contact outputs.
A fault is indicated by a red LED.
The device is easily configured by the use of DIP switches or software.
The device can be powered via terminals or Power Bus.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Product Overview SC-System | ENG | 456 KB | |
Tender text | |||
Tender text | ENG | D81 | 12 KB |
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Brief instructions | ENG | 167 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 126 KB | |
Manuals | |||
System Manual | ENG | 2706 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 4814 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 82 KB |
EPLAN macros SC-System devices (EDZ) / EPLAN-Makros SC-System-Geräte (EDZ) | ALL | ZIP | 4082 KB |
Declaration of Conformity | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
EU Declaration of Conformity (P+F) | TDOC-2695CENG | ENG | 172 KB |
Software Tools | Release Info | File Type | File Size |
---|---|---|---|
Configuration software for SC-System: SC-Config / Konfigurations Software für SC-System: SC-Config | 3.4.0 | ZIP | --- |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|