Serviceline Industrial Sensors
Serviceline Explosion Protection

IO-Link master ICE3-8IOL-G65L-V1D-Y

ICE3-8IOL-G65L-V1D-Y
  • Primary version is ICE3-8IOL-G65L-V1D
  • PROFINET IO with Modbus/TCP enabled and OPC UA support
  • Web-based configuration of module and IO-Link devices
  • Integrated IODD storage for more than 100 IODDs
  • Downloadable module configuration
  • M12 L-coded power connector

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICE3-8IOL-G65L-V1D-Y

Product Description
Firmware variant from ICE3-8IOL-G65L-V1D with Modbus enabled by default
General specifications
UL File NumberE360395
Indicators/operating means
LED indicationsee manual
Rotary switchSetting the IP address
Electrical specifications
Rated operating voltage20 ... 30 V DC
General informationM12, L-coded
Nominal voltage24 V DC
Current consumptiontyp. 120 mA
Current loading capacityMax. 2 x 16 A per module
(Loop-through current via L-coded power supply)
Total current: max. 6.7 A per module
Galvanic isolationbetween US and UA
Interface 1
Interface typeIndustrial Ethernet
Physical M12, D-coded
ProtocolPROFINET IO with media redundancy protocol (MRP) + Modbus TCP + OPC UA + MQTT
Modbus max PDI: 33 times / sec
OPC UA max PDI update rate: 20 times / sec
MQTT max PDI update rate: 10 times / sec
Transfer rate10/100 Mbps
Inputs/Outputs
Number/Type8 x IO-Link Class A (X1 – X8)
Configurable as:
Max. 8 IO-Link and 8 digital inputs
Max. 16 digital inputs
Max. 8 digital inputs and 8 digital outputs
short-circuit protected
Sensor supplyPort 1: max. 1.6 A Via L+ (pin 1)
Port 3: max. 1 A via L+ (pin 1)
Ports 2 and 4 – 8: max. 500 mA per port via L+ (pin 1)
Output currentmax. 200 mA Per port via C/Q (pin 4)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2 , EN 61000-6-4
Standard conformity
Degree of protectionEN 60529
Fieldbus standardIEC 61131-2
Electrical safetyCSA C22.2 No. 61010-1-12
UL 61010-1, IEC 61010-2-201
Emitted interferenceEN 61000-6-4, FCC Part 15 Subpart B, ICES-001, AS/NZS CISPR 11
Noise immunityEN 61000-6-2 , EN 61131-2 , EN 61131-9
Shock resistanceEN 60068-2-27
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 95 %
Altitude0 ... 2000 m
Shock and impact resistance15g, 11ms, half-sine
Mechanical specifications
Degree of protectionIP67
ConnectionPower Supply M12, L-coded
Fieldbus M12, D-coded
Inputs/Outputs M12, A-coded
Material
HousingMolded Polyamide 66
Mass454 g
Tightening torque, fastening screws8 Nm
Tightening torque, cable gland0.6 Nm
Dimensions65 mm 30 mm 212 mm
Height212 mm
Width65 mm
Length30 mm
MountingMachine or panel

Classifications

SystemClasscode
ECLASS 13.027242608
ECLASS 12.027242608
ECLASS 11.027242608
ECLASS 10.0.127242608
ECLASS 9.027242608
ECLASS 8.027242608
ECLASS 5.127242608
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICE3-8IOL-G65L-V1D-Y

Function

The module is a PROFINET IO fieldbus module with 8 type A IO-Link master ports according to IO-Link standard V1.1.

The fieldbus module serves as an interface between the controller of a PROFINET IO fieldbus system and IO-Link devices in the field level. The integrated web server and IODD interpreter enabling complete configuration of the fieldbus module and attached IO-Link devices without the need for special software tools. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured. The module is capable of storing all configuration enabling stand-alone usage without a higher-level PLC. MutliLink simultaneously provides data access via different communication protocols like PROFINET IO, Modbus/TCP and OPC UA to multiple controllers. An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A.

The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.

Status information for each channel is displayed via LEDs as a diagnostic function.

Informative Literature: ICE3-8IOL-G65L-V1D-Y

Language Selection:
LiteratureLanguageFile TypeFile Size
Product Overview - IO-Link-Master with OPC UA InterfaceENGPDF1504 KB
Application Report - Industrial Communication - IO-Link Master - CNC MachinesENGPDF757 KB
Application Report - Seamless Communication from the Sensor to the CloudENGPDF171 KB

Product Documentation: ICE3-8IOL-G65L-V1D-Y

Language Selection:
ManualsLanguageFile TypeFile Size
ICE3-8IOL-G65L-V1D and ICE3-8IOL-K45S-RJ45 ManualENGPDF26657 KB
IO-Link Master Modbus Read/Write ExampleENGPDF1028 KB
REST API AddendumENGPDF3039 KB

Design / Simulation: ICE3-8IOL-G65L-V1D-Y

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP6572 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ63 KB

Approvals: ICE3-8IOL-G65L-V1D-Y

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Canada, USA UL ULE360395ALLLINK---
KoreaR-R-PF1-C0087ALLPDF316 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4275EALLPDF111 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5810AALLPDF108 KB

Software: ICE3-8IOL-G65L-V1D-Y

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
PROFINET GSDML files (GSDML-V2.35-Pepperl+Fuchs-ICE38IOL-Y-20210801) / PROFINET GSDML-Dateien (GSDML-V2.35-Pepperl + Fuchs-ICE38IOL-Y-20210801)September 2021ZIP15 KB
Software Tools
PortVision DX v6.02 / PortVision DX v6.022020-08ZIP29584 KB

Associated Products: ICE3-8IOL-G65L-V1D-Y

Accessories

Male connector M12 straight D-coded 4-pin, for cable diameter 5 - 8 mm, shielded, field-attachablefa

Male connector M12 straight A-coded 4-pin, for cable diameter 6 - 8 mm, field-attachablefa
Cordset M12 socket straight to M12 plug straight L-coded, 5-pin, PUR cable grey, UL approvedfa
Female cordset single-ended M12 straight L-coded, 5-pin, PUR cable grey, UL approvedfa
Female connector M12 straight L-coded 5-pin, for cable diameter 8 - 13 mm, field-attachablefa
Ethernet bus cable M12 plug straight D-coded to RJ45 Ethernet-coded, 4-pin, PUR cable green, Cat5e, shielded, drag chain suitablefa
Ethernet bus cable M12 plug straight to M12 plug straight D-coded, 4-pin, PUR cable green, Cat5e, shielded, UL approved, drag chain suitablefa
Y connection cable M12 plug straight A-coded 4-pin to 2x M12 socket straight A-coded 4-pin, 2x PUR cable weld spatter resistant black, UL approved, drag chain suitable, torsion resistantfa
Blind plug for M12 socketsfa
torque screwdriver (0.6 Nm)fa
plug-in cap M12fa
I/O hub with IO-Link interface for 16 digital inputsfa
I/O hub with IO-Link interface for 10 digital inputs and 6 digital outputsfa
I/O hub with IO-Link interface for 16 digital inputs/outputsfa
I/O hub with IO-Link interfacefa
IO-Link converter with analog input (current/voltage)fa
IO-Link converter with analog output (current/voltage)fa
Y connection cable M12 socket straight A-coded 5-pin to M12 plug straight A-coded 3-pin / M12 plug straight A-coded 5-pin, 2x PUR cable black, drag chain suitable, torsion resistantfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!