General specifications |
Signal type | Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Systematic capability (SC) | SC 3 |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 30 V DC |
Ripple | ≤ 10 % |
Rated current | 30 ... 20 mA |
Power dissipation | ≤ 1.1 W including maximum power dissipation in the output |
Input |
Connection side | field side |
Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Pulse/Pause ratio | min. 100 µs / min. 100 µs |
Output |
Connection side | control side |
Connection | output I: terminals 7, 8 ; output II: terminals 10, 11 |
Rated voltage | 30 V DC |
Rated current | 100 mA , short-circuit protected |
Response time | ≤ 200 µs |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current ≤ 10 µA) |
Output I | signal ; Transistor |
Output II | signal ; Transistor |
Collective error message | Power Rail |
Transfer characteristics |
Switching frequency | ≤ 5 kHz |
Galvanic isolation |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2001 |
Input | EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | EXA 16 ATEX 0016 X |
| Marking | II 3(1)G Ex nA [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Voltage | 10.5 V |
| Current | 17.1 mA |
| Power | 45 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Output | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0424 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx EXA 16.0009X |
| IECEx marking | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |