Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging

Inductive sensor NBN40-U1K-E2-3G-3D

NBN40-U1K-E2-3G-3D
  • Sensor head bidirectional and rotatable
  • 4 LEDs indicator for 360° visibility
  • 40 mm non-flush
  • 3-wire DC
  • ATEX/IECEx Zone 2/22

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  NBN40-U1K-E2-3G-3D

General specifications
Switching functionNormally open (NO)
Output typePNP
Rated operating distance40 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 32.4 mm
Actual operating distance36 ... 44 mm typ. 40 mm
Reduction factor rAl 0.31
Reduction factor rCu 0.3
Reduction factor r304 0.74
Reduction factor rBrass 0.39
Output type3-wire
Nominal ratings
Operating voltage10 ... 30 V DC
Switching frequency0 ... 150 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 2 V
Voltage drop at IL
Voltage drop IL = 1 mA, switching element on0.5 ... 2.3 V typ. 0.9 V
Voltage drop IL = 10 mA, switching element on0.8 ... 2.2 V typ. 1.4 V
Voltage drop IL = 20 mA, switching element on0.9 ... 2.3 V typ. 1.5 V
Voltage drop IL = 50 mA, switching element on0.9 ... 2.5 V typ. 1.6 V
Voltage drop IL = 100 mA, switching element on1 ... 2.6 V typ. 1.8 V
Voltage drop IL = 200 mA, switching element on1.2 ... 2.8 V typ. 2 V
Operating current0 ... 200 mA
Off-state current0 ... 0.5 mA typ. 0.01 mA
Off-state current TU =40 °C, switching element off≤ 100 µA
No-load supply current≤ 20 mA
Time delay before availability80 ms
Operating voltage indicatorLED, green
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1358 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN IEC 60947-5-2
Approvals and certificates
IECEx approval
Equipment protection level Gc (ec)IECEx TUR 21.0019X
Equipment protection level Dc (tc)IECEx TUR 21.0020X
ATEX approval
Equipment protection level Gc (ec)TÜV 20 ATEX 8525 X
Equipment protection level Dc (tc)TÜV 20 ATEX 8526 X
UL approvalcULus Listed, General Purpose
Marine approvalDNVGL TAA0000160
Ambient conditions
Ambient temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection typescrew terminals
Information for connectionA maximum of two conductors with the same core cross section may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 %
Core cross sectionup to 2.5 mm2 , stripped insulation length: 7 mm
Minimum core cross-sectionmin. 0.5 mm2 (incl. wire-end ferrules when using flexible conductors)
Maximum core cross-sectionmax. 2.5 mm2 (incl. wire-end ferrules when using flexible conductors)
Connection (system side)screw terminals , M20 x 1.5 cable gland , usable thread length 9.1 mm , screw-in depth max. 9.1 mm
Housing materialPA
Sensing facePA
Degree of protectionIP68 / IP69K
Mass225 g
Dimensions
Height40 mm
Width40 mm
Length118 mm
NoteTightening torque: 1.8 Nm (housing)
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NBN40-U1K-E2-3G-3D

Product Documentation: NBN40-U1K-E2-3G-3D

Taalkeuze:
Product informationTaalBestandstypeBestandsgrootte
Installation conditionsENGPDF195 KB
Safety and Security Documentation
HandleidingHOLPDF238 KB

Design / Simulation: NBN40-U1K-E2-3G-3D

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP2003 KB
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ62 KB

Approvals: NBN40-U1K-E2-3G-3D

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
- DNV GL MarineTAA0000160 Rev. No: 2ALLPDF375 KB
Brasil BR TUV Rheinland Brazil Ex ecTÜV 22.0562 XALLPDF1100 KB
Brasil BR TUV Rheinland Brazil Ex tcTÜV 23.0984 XALLPDF1091 KB
Canada USA UL Ordinary LocationUL-US-2123898-3 / UL-CA-2119599-3ALLPDF283 KB
China SITIIAS CCC Ex Certificate Ex ec2024322315005962 (PT.Pepperl and Fuchs Bintan)ALLPDF4955 KB
China SITIIAS Ex tc CCC Ex Certificate2024322315005982 (PT.Pepperl and Fuchs Bintan)ALLPDF5335 KB
Europe TUV Rheinland ATEX ec 3GTÜV 20 ATEX 8525 XALLPDF524 KB
Europe TUV Rheinland ATEX tc 3DTÜV 20 ATEX 8526 XALLPDF4375 KB
Worldwide TUV Rheinland IECEx ecIECEx TUR 21.0019XALLLINK---
Worldwide TUV Rheinland IECEx tcIECEx TUR 21.0020XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-5064CHOLHOLPDF1402 KB
UK Declaration of Conformity (P+F)TDOC-6460CENGENGPDF1377 KB

Aanverwante producten: NBN40-U1K-E2-3G-3D

Accessories
Modular mounting bracket fa
Adapter platefa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont met Active Shielding Technology

De inductieve VariKont-sensoren met Active Shielding Technology bieden grote schakelafstanden, ongeacht de montageomstandigheden of omgevingsinvloeden. Haal voordeel uit vereenvoudigd installatieontwerp en beperkte kosten!

Inductive Safety Sensors SIL 2 PL d

Gezien de SIL 2-/PL d-geclassificeerde inductieve veiligheidssensoren geen dode zone hebben, kan de gegevensoverdracht worden gewaarborgd zonder handhaving van een minimumafstand tussen sensor en doel. Ontdek onze geoptimaliseerde portfolio voor zware industriële omgevingen.