Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging

Inductive sensor NCN3-F31-N4-V16-K

NCN3-F31-N4-V16-K
  • Direct mounting on standard actuators
  • Fixed setting
  • Usable up to SIL 2 acc. to IEC 61508
  • ATEX & IECEX certifications


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  NCN3-F31-N4-V16-K

General specifications
Switching function2 x normally closed (NC)
Output typeNAMUR
Rated operating distance3 mm
Installationflush mountable
Assured operating distance0 ... 2.4 mm
Actual operating distance2.7 ... 3.3 mm typ.
Actuating elementStainless steel 1.4305 / AISI 303
8.5 mm x 8.5 mm x 0.5 mm
Reduction factor rAl 0.5
Reduction factor rCu 0.4
Reduction factor r304 1
Reduction factor rSt37 1.3
Reduction factor rBrass 0.6
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 3 kHz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected≥ 3 mA
Measuring plate detected≤ 1 mA
Time delay before availability≤ 1.1 ms
Switching state indicatorLED, yellow
Valve status indicatorLED, yellow
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
MTTFd1470 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Valve circuit
Voltagemax. 32 V DC
Currentmax. 240 mA
Short-circuit protectionno
Reverse polarity protectionyes, with reversed output LED is out of function, therfore more power for solenoid valve
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN IEC 60947-5-2
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx TUN 17.0021X
Equipment protection level GbIECEx TUN 17.0021X
Equipment protection level MbIECEx TUN 17.0021X
ATEX approval
Equipment protection level GaTÜV 99 ATEX 1479 X
Equipment protection level GbTÜV 99 ATEX 1479 X
Equipment protection level Gc (ic)PF13CERT2895 X
UL approvalcULus Listed, General Purpose
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0456
CCC approval
Hazardous Location2020322315002262
NEPSI approval
NEPSI certificateGYJ19.1410X
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection (system side)Connector plug Rd24 x 1/8 , 7-pin
Connection (valve side)PVC cable , 0.5 m
Core cross section (valve side)0.75 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP67
Cable
Cable diameter6 mm ± 0.2 mm
Bending radius> 10 x cable diameter
Tightening torque, fastening screws4 Nm ... 5 Nm
Dimensions
Height33.5 mm
Width65 mm
Length36 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027273901
ECLASS 12.027273901
ECLASS 11.027220501
ECLASS 10.0.127220501
ECLASS 9.027220501
ECLASS 8.027220501
ECLASS 5.127220501
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NCN3-F31-N4-V16-K

Product Documentation: NCN3-F31-N4-V16-K

Taalkeuze:
Safety and Security DocumentationTaalBestandstypeBestandsgrootte
Instruction manualENGPDF185 KB

Design / Simulation: NCN3-F31-N4-V16-K

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP385 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ270 KB

Approvals: NCN3-F31-N4-V16-K

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Canada USA UL Hazardous LocationE501628:1:6ALLPDF474 KB
Canada USA UL Ordinary LocationUL-US-2140224-1 / UL-CA-2133715-1ALLPDF491 KB
China NEPSIGYJ19.1410XALLPDF2028 KB
China SITIIAS CCC Ex Certificate2020322315002262 (Trutnov)ALLPDF2855 KB
EU Pepperl+Fuchs Certificate Ex ic ATEX Category 3 GPF13CERT2895XALLPDF123 KB
EU TUV Nord ATEX ia 2G, 1G, 1D s. certificateTÜV 99 ATEX 1479 XALLPDF662 KB
United Kingdom CML UKEX Category I M2 UKEX Category II 2 G UKEX Category II 1 D UKEX Category II 1 GCML 21UKEX21289XALLPDF298 KB
Worldwide Pepperl+Fuchs Functional Safety CertificatePF12CERT2382GALLPDF1492 KB
Worldwide TUV Nord IECEx iaIECEx TUN 17.0021XALLLINK---
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF378 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-5076AALLPDF1232 KB
UK Declaration of Conformity (P+F)TDOC-6562AENGENGPDF1229 KB

Aanverwante producten: NCN3-F31-N4-V16-K

Accessories

fa

fa

fa
fa
fa
fa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont met Active Shielding Technology

De inductieve VariKont-sensoren met Active Shielding Technology bieden grote schakelafstanden, ongeacht de montageomstandigheden of omgevingsinvloeden. Haal voordeel uit vereenvoudigd installatieontwerp en beperkte kosten!

Inductive Safety Sensors SIL 2 PL d

Gezien de SIL 2-/PL d-geclassificeerde inductieve veiligheidssensoren geen dode zone hebben, kan de gegevensoverdracht worden gewaarborgd zonder handhaving van een minimumafstand tussen sensor en doel. Ontdek onze geoptimaliseerde portfolio voor zware industriële omgevingen.