General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 19 ... 30 V DC |
Ripple | within the supply tolerance |
Rated current | < 28 mA |
Power consumption | 0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current) |
Input |
Connection side | field side |
Connection | terminals 1, 2, 3, 4 |
Line fault detection | yes , at Pt100 |
Lead resistance | ≤ 10 % of resistance value |
Transmission range | 0 ... 10 mA |
Available voltage | 7 V |
Line fault detection | < 30 nA |
Output |
Connection side | control side |
Connection | terminals 5-, 7-, 6+, 8+ |
Current | 0 ... 10 mA |
Available voltage | 0 ... 4.2 V |
Fault signal | field voltage < 150 mV or > 4 V, depending on lead disconnected |
Reverse polarity protection | for I < 10 mA or U < 20 V |
Transfer characteristics |
Accuracy | 0.1 % |
Deviation | Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable). |
| Influence of ambient temperature | Im ≥ 1 mA, Rm ≥ 100 Ω: 0.01 %/K in the range -20 ... +70 °C (-4 ... 158 °F) Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm |
Settling time | ≤ 5 ms |
Rise time/fall time | ≤ 2 ms (10 ... 90%) |
Galvanic isolation |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2017 EN IEC 61326-3-2:2018 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1:2012 |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | spring terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 |
| Height | 124 mm |
| Width | 12.5 mm |
| Depth | 114 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BASEEFA 10 ATEX 0061X |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage | 9.5 V |
| Current | 39.22 mA |
| Power | 93 mW |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Output | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Certificate | BASEEFA 10 ATEX 0062X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
FM approval | |
| FM certificate | FM 19 CA 0039 X , FM 19 US 0067 X |
| Control drawing | 116-0457 (cFMus) |
UL approval | E106378 |
| Control drawing | 116-0332 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx BAS 10.0024X IECEx BAS 10.0025X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |