General specifications |
Signal type | Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Ripple | ≤ 10 % |
Rated current | ≤ 30 mA |
Power dissipation | ≤ 600 mW |
Power consumption | ≤ 600 mW |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
Rated values | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.7 mA |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output |
Connection side | control side |
Connection | SL1: 8a, 7a; 10a, 9a |
Output I | signal ; relay |
Output II | signal ; relay |
Contact loading | 50 V DC / 0.5 A |
Minimum switch current | 2 mA / 24 V DC |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Mechanical life | 107 switching cycles |
Fault indication output |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics |
Switching frequency | ≤ 10 Hz |
Galvanic isolation |
Output/power supply | basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC |
Output/Output | basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Galvanic isolation | EN 50178:1997 |
Electromagnetic compatibility | EN IEC 61326-3-2:2018 , NE 21:2012 For further information see system description. |
Degree of protection | IEC 60529:2001 |
Input | EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 110 g |
Dimensions | 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D) |
| Height | 106 mm |
| Width | 12.5 mm |
| Depth | 128 mm |
Mounting | on termination board |
Coding | pin 1 and 2 trimmed For further information see system description. |
Data for application in connection with hazardous areas |
EU-type examination certificate | BASEEFA 06 ATEX 0093 X |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage | 10.5 V |
| Current | 17.1 mA |
| Power | 45 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Output | |
| Contact loading | 50 V DC / 0.5 A |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Certificate | PF 08 CERT 1047 X |
| Marking | II 3G Ex nA nC IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 16-534FM-12 (cFMus) |
UL approval | E106378 |
| Control drawing | 116-0434 |
IECEx approval | |
| IECEx certificate | IECEx BAS 06.0026X |
| IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |