LB9006C Power supply

Key Benefits at a Glance

  • Power supply for 24 V
  • Permits vertical or horizontal mounting in Zone 2
  • Use three power supplies for redundancy
  • Galvanic isolation to mains
  • Supply of I/O modules and com units
  • Mounting in Zone 2, Class I/Div.2 or in the safe area

Show more

In stock523,20 EUR Net price—your individual price will be shown during checkout process.
Approval
Product Compliance: Europe – CE
Note

All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

DE
  • DE
  • EN

Technical data of LB9006C

Bus coupler2
I/O modules>12, depending on the type
Maximum safe voltage Um60 V DC (SELV/PELV)
Input voltage rangeU18 ... 32 V DC (SELV/PELV)
Power dissipationapprox. 15 % of power consumption
Power consumptionmax. 30 W for Zone 2 applications
max. 45 W for applications in safe area
parallel connection with other LB9006C (autom. power sharing)
Inrush current1.5 A (10 ms)
Voltage5.4 V DC +/- 5% ,
12 V DC + 4/- 2%
PowerP5V ≤ 5.4 W, P12V ≤ 25 W - P5V for Zone 2 applications
P5V ≤ 5.4 W, P12V ≤ 39 W - P5V for applications in safe area
LED indicationPower LED (P) green: OFF in case of loss of 24 V or 12 V or 5 V
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-78
Ambient temperature-40 ... 60 °C (-40 ... 140 °F) , 70 °C (non-Ex)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Altitudemax. 2000 m
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protectionIP20 (module) , mounted on backplane
Massapprox. 220 g
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
CertificatePF 08 CERT 1234 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Galvanic isolation
Output/power supply, internal busEN 60950-1 (Safety requirement: < 60 V, external supply SELV/PELV)
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020
EN 60079-15:2010
ATEX approvalPF 08 CERT 1234 X
UL approvalE106378
IECEx approval
IECEx certificateIECEx BVS 09.0037X
IECEx markingEx nA IIC T4 Gc
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
General Notes