Select Your Country
LCL1 Capacitive limit switch
Key Benefits at a Glance
- Limit switch for bulk solids
- Device with rod probe
- Complete unit consisting of the probe and electronic insert
- Integrated active build-up compensation: exact switch point, even with strong build-up
- Mechanically rugged: no wearing parts, long operating life, maintenance-free
Show more


Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
DE
- DE
- EN
Technical data of LCL1
Measuring method | A metal plate at the end of the probe, within the insulation, and the surroundings (e. g. the silo walls) combine to form the two electrodes of a capacitor. If the probe is covered or free of material, then the capacitance changes and the LCL switches. | |
Equipment architecture | The measuring system consists of: - the device - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
Construction type | device with rod probe | |
Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
Series | LCL1 |
Rated voltage | Ur | electrical connection E5: 10.8 ... 45 V DC, short-term pulse on 55 V DC electrical connection WA: 20 ... 235 V AC, 50/60 Hz or 20 ... 55 V DC |
Current consumption | electrical connection E5: max. 30 mA, reverse-polarity-proof electrical connection WA: max. 130 mA |
Surge protection | overvoltage category III |
Measured variable | limit level (limit value) | |
Measuring range | dielectric constant ≥ 1.6 |
Switch-on delay | ton | correct switching after max. 1.5 s |
Output signal | connection E5: switching PNP, Imax = 200 mA - overload and short circuit protection - residual voltage at transistor at Imax < 2.9 V connection WA: contact change-over, potential-free - Umax = 253 V - Imax = 4 A (AC) - Pmax = 1000 VA, cos φ = 1, Pmax = 500 VA, cos φ > 0.7 | |
Signal on alarm | connection E5: < 100 µA connection WA: relay de-energized |
Electromagnetic compatibility | |||||
| |||||
Low voltage | |||||
|
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | EN 60068, part 2-38 (test Z/AD) |
Reference operating conditions | vessel type: plastic vessel, ambient temperature: 73 °F (23 °C, 296 K), medium temperature: 73 °F (23 °C, 296 K) medium pressure pe: 0 bar, medium: dielectric constant = 2.6, conductivity: < 1 µS sensitivity setting: C | |
Hysteresis | horizontal 4 mm (0.16 inch), vertical 7 mm (0.28 inch) | |
Long-term drift | horizontal 3 mm (0.12 inch), vertical 6 mm (0.24 inch) | |
Influence of medium temperature | depending on the filling material | |
Switching time | approx. 0.5 s when covering and uncovering the sensor |
Installation conditions | |||||||||||||||||
| |||||||||||||||||
Process conditions | |||||||||||||||||
|
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) -40 ... 60 °C (-40 ... 140 °F) (Dust-Ex version) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Shock resistance | device with F34 housing: 7 J | |
Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h |
Degree of protection | IP66, NEMA 4 | |
Connection | gland M20 thread G1/2, NPT1/2 | |
Material | F14 housing: polyester PBT-FR F34 housing F34: aluminum Probe: PPS GF40 | |
Dimensions | max. ∅94 mm (3.7 inch), length 391 mm (15.4 inch) | |
Process connection | thread R1 acc. to EN 10226, BSPT, adapter for R1-1/2 and G1-1/2 see accessories thread NPT1 to ANSI B 1.20.1, adapter for NPT1-1/4 see accessories |
EU-type examination certificate | see instruction manuals (SI) | ||||
Directive conformity | |||||
|
Supplementary documentation | technical information (TI) manuals, brief instructions (BA, KA) instruction manuals (SI) | |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Designation | - LCL-Z10 cover with sight glass for F14 housing - LCL-Z11 adapter for R1-1/2, EN 10226 - LCL-Z12 adapter for G1-1/2, DIN ISO 228 - LCL-Z13 adapter for NPT1-1/4, steel - LCL-Z15 adapter for NPT1-1/4, 1.4571 |
Related News and Applications