KE switch cabinet module, 4 inputs (PNP) and 3 relay outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V2.1 | |
Required gateway specification | ≥ V2.1 | |
Profile | S-7.A.0 | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 0 | |
UL File Number | E106378 | |
Indicators/operating means | ||
LED FAULT | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
|
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; LED green | |
LED IN | switching state (input); 4 LED yellow | |
LED OUT | Switching state (output); 3 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (input) | 12 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 35 mA (without sensors) / max. 235 mA | |
Surge protection | O1 ... O3: Over voltage category II UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) |
|
Input | ||
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC | |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) | |
Voltage | 21 ... 31 V DC (INT) | |
Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) | |
Input current | ≤ 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 2 mA | |
1 (attenuated) | ≥ 4 mA | |
Signal delay | < 2 ms (input/AS-Interface) | |
Signal frequency | ≤ 250 Hz | |
Output | ||
Number/Type | 3 relay outputs, normally open | |
Supply | none | |
Nominal load | ||
Per contact | max. 2 A / 30 V DC; 2 A / 250 V AC | |
Per module | 6 A | |
Minimum load | ||
Per contact | 10 mA / 5 V DC | |
Short-circuit-proof | Contact: 500 A / 40 ms | |
Switching off power | 500 VA | |
Switching delay | < 10 ms (AS-Interface/contact) | |
Usage category | DC-13 and AC-14 | |
Switching frequency | < 20 Hz (without load) < 0.1 Hz (nominal load) |
|
Switching | ||
Mechanical | 30 x 106 | |
Electrical | 1 x 106 switching cycles (40 V DC, 2 A, ohmic) 0.5 x 106 switching cycles (253 V AC, 2 A, cos φ = 1) 0.45 x 106 switching cycles (253 V AC, 2 A, cos φ = 0.7) |
|
Galvanic isolation | ||
Input/Output | IN1 ... IN4 to O1 ... O3: safe isolation acc. to EN 60947-1, rated insulation voltage 278 V AC |
|
Input/AS-Interface | none | |
Output/Output | O1 to O2, O3: safe isolation according to EN 60947-1, rated insulation voltage 278 V AC O2 to O3: basic insulation according to EN 60947-1, rated insulation voltage 278 V AC |
|
Output/AS-Interface | safe isolation acc. to EN 60947-1, rated insulation voltage 278 V AC |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | |
Low voltage | ||
Directive 73/23/EEC | EN 60947-1:2007 | |
Standard conformity | ||
Galvanic isolation | EN 60947-1 | |
Electromagnetic compatibility | NAMUR NE 21: 1998-08 | |
Degree of protection | EN 60529:2000 | |
Pollution degree | EN 60947-5-1 | |
Input | EN 61131-2:2004 | |
Usage category | EN 60947-5-1 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005 | |
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
|
Material | ||
Housing | PA 66-FR | |
Mass | 170 g | |
Dimensions | ||
Height | 99 mm | |
Width | 22.5 mm | |
Length | 102 mm | |
Mounting | DIN mounting rail | |
Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 605 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 112 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada UL cUL | E106378 cUL (QUZW7) | ALL | LINK | --- |
USA UL | E106378 UL (QUZW) | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 43201 | ALL | 608 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability