Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Ladda ned datablad som PDF::
Product Description |
---|
CB10 safety module, 2 safety-related inputs and 2 conventional electronic outputs |
General specifications | ||
---|---|---|
Node type | Safety-Slave | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 |
|
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
|
LED IN | switching state (input); 2 LED yellow | |
LED OUT | Switching state (output); 2 LED yellow | |
Electrical specifications | ||
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface (PELV) |
|
Rated operating current | ≤ 40 mA (without inputs/outputs)/max. 160 mA | |
Protection class | III | |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) | |
Rated insulation voltage | 32 V | |
Pulse withstand voltage | 0.8 kV | |
Input | ||
Number/Type | 2 safety-related inputs for mechanical contacts, crossed-circuit monitored: 2 single-channel contacts: Up to category 2/PLc in accordance with ISO 13849-1 or SIL 1 in accordance with IEC 62061 1 two-channel contact: Up to category 4/PLe in accordance with ISO 13849-1 or SIL 3 in accordance with IEC 62061 |
|
Supply | from AS-Interface | |
Voltage | 20 ... 30 V DC pulsed | |
Current | input current limited ≤ 15 mA, short-circuit protected |
|
Output | ||
Number/Type | 2 conventional electronic outputs, PNP , overload and short-circuit resistant | |
Supply | from AS-Interface | |
Voltage | (UASI - 7.0 V) ≤ UOUT ≤ UASI | |
Current | ≤ 100 mA per output, ≤ 100 mA total | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | IEC 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 EN 61326-1:2013 | |
Machinery Directive | ||
Directive 2006/42/EC | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Electrical safety | IEC 61140:2009 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | IEC 62026-2:2013 EN 61326-3-1:2017 EN 61000-6-2:2005 | |
Functional safety | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 | |
Programming instructions | ||
Profile | S-7.B | |
IO code | 7 | |
ID code | B | |
ID1 code | F | |
ID2 code | 0 | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | not used | |
P1 | not used | |
P2 | not used | |
P3 | not used | |
Approvals and certificates | ||
UL approval | Protection class IP20 is not included in the UL approval. The protection class is tested by Pepperl+Fuchs. | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 5000 m above MSL | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 2000 Hz, 10 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 according to EN 60529 | |
Connection | 200 mm, PVC cable 0.5 mm2 |
|
Material | ||
Contacts | open conductor ends with connector sleeves | |
Housing | Polyamide hot-melt adhesive | |
Mass | 31 g | |
Dimensions | ||
Height | 10.1 mm | |
Width | 36 mm | |
Length | 39.5 mm | |
Note | This device is maintenance-free. If the device is used in a manner not specified by the manufaturer, the protection provided by the device may be impaired. |
System | Classcode |
---|---|
ECLASS 13.0 | 27272603 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 170 KB | |
Manuals | |||
Manual VAA-2E*A-CB10-SJ/E2J-FL | ENG | 986 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Functional Safety Certificate | 968/FSP 2012.00/20 | ALL | 620 KB | |
US CA UL | E223772 | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 134801 | ALL | 135 KB | |
Declaration of Conformity | ||||
EU-försäkran om överensstämmelse | TDOC-4592CSWE | SWE | 194 KB | |
UK-Declaration of conformity | TDOC-7060_ENG | ENG | 171 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|