Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Ladda ned datablad som PDF::
Utdrag ur datablad: Tekniska data för
KCD2-E1
Product Description |
Sensor output interface terminal |
Functional safety related parameters |
MTTFd | 1612 a |
Indicators/operating means |
LED yellow | switch output |
Electrical specifications |
Operating voltage | 10 ... 30 V DC |
Ripple | ≤ 10 % |
Operating current | approx. 22 mA |
Input |
Connection | terminals 1+, 2- |
Connectable sensor types | NAMUR |
Pulse length/pulse interval | ≥ 0.5 ms / ≥ 0.5 ms |
Short-circuit current | approx. 8 mA |
Sensor supply | 8 V DC |
Switching point | 1.2 ... 2.1 mA hysteresis approx. 0.2 mA |
Line fault detection | without |
Trip value | 1 kHz |
Output |
Connection | terminal 4- |
Current | 200 mA short-circuit protected |
Transistor | NPN |
Signal level | UB - 1.8V |
Transfer characteristics |
Mode of operation | NC contact |
Switching frequency | 1 kHz |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Noise immunity | EN 61326-1:2013 |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications |
Connection | self-opening apparatus connection terminals, max. core cross-section 0.34 ... 2.5 mm2 |
Mass | 60 g |
Dimensions | 20x60x40 (in mm) |
Classifications
System | Classcode |
ECLASS 13.0 | 27210121 |
ECLASS 12.0 | 27210121 |
ECLASS 11.0 | 27210121 |
ECLASS 10.0.1 | 27210121 |
ECLASS 9.0 | 27210121 |
ECLASS 8.0 | 27210121 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC002653 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC002653 |
UNSPSC 12.1 | 41111902 |
Details:
KCD2-E1
Design / Simulation:
KCD2-E1