工業感測器服務資訊
+886 2 27227708
+886-2-27227782
防爆產品服務資訊

Thermocouple Converter KFD0-TT-Ex1

KFD0-TT-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Thermocouple input
  • Output 4 mA ... 20 mA
  • Internal cold junction compensation
  • Sensor breakage detection
  • DIP switch selectable ranges

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

將完整的規格書下載為PDF:


產品規格摘要:的技術資料  KFD0-TT-Ex1

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power dissipation0.4 W
Input
Connection sidefield side
Connectionterminals 1+, 2-, 3- thermocouple E, J, K, N, R, S or T, cold junction referenced to 0 °C (32 °F)
Lead resistancemax. 100 Ω per line
Currentlead monitoring ON: ≤ 15 nA; OFF: ≤ 1 nA
Output
Connection sidecontrol side
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to ≤ 35 mA
Fault signaldownscaling ≤ 3 mA , upscaling ≥ 22 mA
Transfer characteristics
Measuring rangespan 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable
Deviation
After calibration0.1 % of full-scale value ± 1 K for the cold junction
Temperature effect temperature deviation 0.015 % of the span/K or 1.5 µV/K cold junction ± 2 K (calibrated at Tamb = 20 °C (68 °F))
Influence of supply voltage6.5 ppm/V
Characteristic curvethe output voltage is linearly proportionate to the input voltage (not to temperature)
Rise time250 ms
Galvanic isolation
Input/Outputsafe isolation according to EN 50178, rated insulation voltage 253 Veff
Indicators/settings
Control elementsDIP switch
rotary switch
Configurationvia DIP switches
via rotary switch
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateZELM 00 ATEX 0035
MarkingEx-Hexagon II (1)GD [EEx ia] IIC
Voltage16.1 V
Current0.8 mA
Power3.2 mW
Output
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
CertificateTÜV 01 ATEX 1777 X
MarkingEx-Hexagon II 3G Ex nA II T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing116-0132
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD0-TT-Ex1

Informative Literature: KFD0-TT-Ex1

Language Selection:
Literature語言檔案類型檔案尺寸
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD0-TT-Ex1

Language Selection:
Safety and Security Documentation語言檔案類型檔案尺寸
Instruction manualENGPDF50 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD0-TT-Ex1

Language Selection:
CAD語言檔案類型檔案尺寸
CAD 3-D / CAD 3-DALLSTP2510 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ941 KB

Approvals: KFD0-TT-Ex1

Language Selection:
Certificates證書號碼語言檔案類型檔案尺寸
Canada CSACoC 1029981 CALLPDF177 KB
Europe TUV Nord ATEX Category 3TÜV 01 ATEX 1777XALLPDF767 KB
Europe ZELM ATEX Category (1) GDZELM 00 ATEX 0035ALLPDF565 KB
South Africa MASC Zone 2MASC S/17-0871XALLPDF1028 KB
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF54 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0770CENGENGPDF183 KB

相關產品: KFD0-TT-Ex1

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.