工業感測器服務資訊
+886 2 27227708
+886-2-27227782
防爆產品服務資訊

Power Feed Module KFD2-EB2

KFD2-EB2
  • Interface for Power Rail
  • Supply current ≤ 4 A
  • Replaceable fuse
  • Relay contact output, reversible
  • LED status indication

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

將完整的規格書下載為PDF:


產品規格摘要:的技術資料  KFD2-EB2

產品描述
Power Feed Module
Supply
Connectionterminals 11+, 12-
terminals 8+, 9-
Rated voltage20 ... 30 V DC
The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded.
Fusing5 AT/250 V AC
recommended maximum utilization of the fuse: 80 %
Power dissipation≤ 1 W
Output
ConnectionPower Rail
Output currentmax. 4 A
Output voltageUi ≥ rated voltage Ur = Ui - 0.6 V
Fault signalrelay output: NO contact
Contact loading30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificateUL 22 ATEX 2853 X
MarkingEx-Hexagon II 3G Ex ec nC IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN IEC 60079-15:2019
International approvals
FM approvalFM 22 US 0031 X
Control drawing116-0160
UL approvalE106378
CSA approvalCoC 1051840
IECEx approval
IECEx certificateIECEx UL 16.0051X
IECEx markingEx ec nC IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC002542
UNSPSC 12.139121004

Details: KFD2-EB2

Informative Literature: KFD2-EB2

Language Selection:
Literature語言檔案類型檔案尺寸
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB

Product Documentation: KFD2-EB2

Language Selection:
Brief Instructions語言檔案類型檔案尺寸
Instruction leaflet / BeipackzettelALLPDF79 KB
Safety and Security Documentation
Instruction manualENGPDF164 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-EB2

Language Selection:
CAD語言檔案類型檔案尺寸
CAD 3-D / CAD 3-DALLSTP2510 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ57 KB

Approvals: KFD2-EB2

Language Selection:
Certificates證書號碼語言檔案類型檔案尺寸
Canada CSACoC 1051840 CALLPDF43 KB
China SITIIAS CCC Ex Certificate2024322303005906 (Vietnam)ALLPDF1864 KB
China SITIIAS CCC Ex Certificate2020322303003533 (Singapore)ALLPDF844 KB
DNV MarineTAA00001WXALLPDF106 KB
Europe UL ATEX Category 3 GUL 22 ATEX 2853XALLPDF23 KB
Korea KOSHA22-AV4BO-0058XALLPDF67 KB
UL IECEx Certificate of ConformityIECEx UL 16.0051XALLLINK---
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC E106378 RepRef E106378-20160330ALLPDF371 KB
USA FMFM 22 US 0031XALLPDF878 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF146 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0058DENGENGPDF178 KB
UKCA-Declaration of conformity / UKCA-KonformitätserklärungDOC-5299AALLPDF96 KB

相關產品: KFD2-EB2

Accessory of
FieldConnex® Fieldbus, Segment coupler 1, power supply and gateway for PROFIBUS DP to PROFIBUS PA communication, Output: 24 ... 26 V/400 mA, Couples PROFIBUS PA devices transparently to PROFIBUS DP, High-power trunk for high device count and long cable lengths, Installation in Zone 2/Class I, Div. 2, Up to 1.5 MBit auto-adapting, Europe, USA, Canadapa
FieldConnex® Fieldbus, Segment Coupler 1 for coupling PROFIBUS PA devices to PROFIBUS DP, Output: 12.6 ... 13.4 V/100 mA, Couples PROFIBUS PA devices transparently to PROFIBUS DP, Intrinsically safe, Ex ia (FISCO or Entity), Installation in Zone 2/Class I, Div. 2, Fixed, high-availability terminator, IECEx approval, Dust protection, Europe, USA, Canada, Device coupler location: Zone 2 - high-power trunk
Zone 1 - intrinsically safe trunkpa
FieldConnex® Fieldbus, Fieldbus power supply for fieldbus power hub, Output: 25 ... 27 V/360 mA, For most fieldbus applications, High-power trunk for high device count and long cable lengths, Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa
FieldConnex® Fieldbus, Fieldbus power supply with low voltage for compact plants also in island mode, Output: 12 ... 13 V/220 mA, For battery or solar-powered applications, For demanding environmental conditions , Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Division 2 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Matching System Components
2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 15 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Rated voltage: 18 ... 30 V DC, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Line fault detection, Current: ≤ 45 mA, Voltage: ≥ 15 Vpa
2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 15 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Rated voltage: 18 ... 30 V DC, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 2 x Valve, Field device [2]: 2 x audible alarmpa
2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 15 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width: 20 mm, Number of channels: 2-channel, Line fault transparency, Rated voltage: 18 ... 30 V DC, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Line fault detection, Voltage: ≥ 15 Vpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Lead breakage monitoring, Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Signal: 1 x 4 ... 20 mA, Field device: 1 x I/P converterspa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: current source, Signal: 0/4 ... 20 mApa
2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width: 20 mm, Number of channels: 2-channel, Line fault transparency, Rated voltage: 18 ... 30 V DC, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Line fault detection, Voltage: ≥ 12 Vpa
2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width: 20 mm, Number of channels: 2-channel, Line fault transparency, Rated voltage: 18 ... 30 V DC, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Line fault detection, Voltage: ≥ 10 Vpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Voltage output 0 V ... 5 V, Lead resistance compensation adjustment, Accuracy 0.05 %, Housing width: 20 mm, Number of channels: 1-channel, Rated voltage: 20 ... 35 V DC, Type: 3-wire connection, Type [2]: 4-wire connection, Type [3]: 5-wire connection, Field device: potentiometer, Signal: 1 x 0 ... 5 Vpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Analog input (AI), Analog output (AO), Operates as transmitter power supply or current driver, Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (NO contact)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (NO contact)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Rated voltage: 18 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter, Field device [3]: current sourcepa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DC, Field device: 2-wire transmitterpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the control system, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: resistance thermometerpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 3, Rated voltage: 19 ... 30 V DC, Signal: 1 x 4 ... 20 mA, Field device: 1 x I/P converters, Field device [2]: 1 x positionerpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V ... -20 V, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Signal: 1 x -20 ... 0 V, Signal: 1 x -20 ... 0 V, Cut-off frequency: 10 kHz (-0,1 dB)
20 kHz (-1 dB)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the control system, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: resistance thermometer, Signal: Resistancepa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 8 V DC ... 60 V DC, Relay contact output for de-energized to safe function, Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC/EN 61508, Up to PL e acc. to EN/ISO 13849, Housing width: 20 mm, Number of channels: 1-channel, Diagnostics function, Line fault transparency, DTS function (de-energized to safe), Safety Integrity Level (SIL): SIL 3pa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 50 V AC ... 230 V AC, 60 V DC ... 110 V DC, Relay contact output for de-energized to safe function, Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC/EN 61508, Up to PL e acc. to EN/ISO 13849, Housing width: 20 mm, Number of channels: 1-channel, Diagnostics function, Line fault transparency, DTS function (de-energized to safe), Safety Integrity Level (SIL): SIL 3pa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 8 V DC ... 60 V DC, Relay contact output for energized to safe function , Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Diagnostics function, Line fault transparency, ETS function (energized to safe), Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 26.4 V DCpa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 50 V AC ... 230 V AC, 60 V DC ... 110 V DC, Relay contact output for energized to safe function , Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Diagnostics function, Line fault transparency, ETS function (energized to safe), Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3pa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC
loop powered, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 1 x Valvepa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitterpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensorpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensorpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensorpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensorpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensorpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Line fault detection (LFD), Accuracy 0.1 %, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Transfer direction: to the field, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Signal: 2 x 4 ... 20 mA, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA, Terminals with test points, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 35 V DC, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter, Field device [3]: current sourcepa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Housing width 12.5 mm, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: current source, Input signal: 4 ... 20 mA limited to approx. 26 mApa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: current sourcepa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitterpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Active voltage output, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Up to PL d acc. to EN/ISO 13849, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 30 V DC, Field device: SN/S1N sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: current sourcepa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Up to PL d acc. to EN/ISO 13849, Housing width: 40 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 35 V DC, Field device: SN/S1N sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V ... 10 V, Transmission frequency up to 50 kHz, Voltage output -10 V ... 10 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 ... 35 V DC, Signal: 1 x -10 ... 10 V, Signal: 1 x -10 ... 10 V, Cut-off frequency: 50 kHz (-3 dB)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V ... 10 V, Voltage output -10 V ... 10 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 ... 35 V DC, Signal: 1 x -10 ... 10 V, Signal: 1 x -10 ... 10 V, Cut-off frequency: 1.2 kHz (-3 dB)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 12 V, Voltage output 0 V ... 12 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 ... 35 V DC, Signal: 1 x 0 ... 12 V, Signal: 1 x 0 ... 12 V, Cut-off frequency: 1.2 kHz (-3 dB)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 9 V, Voltage output 0 V ... 9 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 ... 35 V DC, Signal: 1 x 0 ... 9 V, Signal: 1 x 0 ... 9 V, Cut-off frequency: 1.2 kHz (-3 dB)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV ... ± 50 mV, Voltage output 0 mV ... ± 50 mV, Selectable up/downscale sensor breakage detection, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 19 ... 30 V DC, Signal: 1 x -50 ... 50 mV, Signal: 1 x -50 ... 50 mV, Cut-off frequency: 350 Hz (-3 dB)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV ... ± 500 mV, Voltage output 0 mV ... ± 500 mV, Selectable up/downscale sensor breakage detection, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 19 ... 30 V DC, Signal: 1 x -500 ... 500 mV, Signal: 1 x -500 ... 500 mV, Cut-off frequency: 350 Hz (-3 dB)pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Voltage output 0/1 V ... 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: 2-wire connection, Type [2]: 3-wire connectionpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: logic input, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Current: ≤ 45 mA, Voltage: ≥ 11.7 Vpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: logic input, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Line fault detection, Current: ≤ 45 mA, Voltage: ≥ 11.7 Vpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Output 20.4 mA at 13.5 V DC, 19 V DC ... 30 V DC input, Test pulse immunity, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Conformal coating, Safety Integrity Level (SIL): SIL 3, Rated voltage: 19 ... 30 V DC, Type: logic input, Field device: 1 x Valve, Field device [2]: 1 x audible alarm, Field device [3]: 1 x visual alarm, Fault indication output, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Current output 4 mA ... 20 mA, Lead resistance compensation adjustment, Accuracy 0.05 %, Housing width: 20 mm, Number of channels: 1-channel, Rated voltage: 20 ... 35 V DC, Type: 3-wire connection, Type [2]: 4-wire connection, Type [3]: 5-wire connection, Field device: potentiometer, Signal: 1 x 4 ... 20 mApa
1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Voltage output 0 V ... 10 V, Lead resistance compensation adjustment, Accuracy 0.05 %, Housing width: 20 mm, Number of channels: 1-channel, Rated voltage: 20 ... 35 V DC, Type: 3-wire connection, Type [2]: 4-wire connection, Type [3]: 5-wire connection, Field device: potentiometer, Signal: 1 x 0 ... 10 Vpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Logic input, Output 100 mA at 13 V DC, Alternating outputs for the operation of solenoids with 2 coils, High output power for IIB gas group, Line fault transparency (LFT), Test pulse immunity, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC
loop powered, Type: logic inputpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Redundant TC input, Current output 0/4 mA ... 20 mA, 2 relay contact outputs, Configurable by PACTware or keypad, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: 2-wire connectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Current output up to 900 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Signal: 1 x 4 ... 20 mApa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Lead breakage monitoring, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Current output up to 900 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Housing width 12.5 mm, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Signal: 1 x 4 ... 20 mA, Field device: 1 x I/P converters, Field device [2]: 1 x positionerpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3pa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DCpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DC, Field device: 2-wire transmitterpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Rated voltage: 18 ... 30 V DC, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter, Field device [3]: current sourcepa
2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DC, Field device: 2-wire transmitterpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Current and voltage input, 2 relay contact outputs, Programmable high/low alarm, Configurable via DIP switches and potentiometer, Terminal blocks with test sockets, Housing width: 20 mm, Number of channels: 1-channel, Test sockets, Programmable high/low alarm, Rated voltage: 20 ... 30 V DC, Signal: 0/4 ... 20 mA, Signal [2]: 0/1 ... 5 V, Type: 2 x relay (change-over contact)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Line fault detection (LFD), Accuracy 0.1 %, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Signal: 2 x 4 ... 20 mA, Line fault detectionpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts, Input frequency 1 mHz ... 10 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Frequency conversion, Rotation speed monitoring, Pulse dividerpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, Application-specific outputs, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, Application-specific outputs, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Application-specific outputs, 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Application-specific outputs, 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA ... 20 mA, Sink and source mode output, Configurable by keypad, Housing width: 40 mm, Number of channels: 1-channel, HART communication, Trip relay, Rated voltage: 19 ... 30 V DC, Function: transmitter supply, Field device: 3-wire transmitterpa
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 3 analog outputs 4 mA ... 20 mA, Sink and source mode output, Configurable by keypad, Housing width: 40 mm, Number of channels: 1-channel, HART communication, Trip relay, Rated voltage: 19 ... 30 V DC, Function: transmitter supply, Field device: 3-wire transmitter, Field device [2]: active sources, Signal: HARTpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
4-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 50 % less wiring, 2:1 technology, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Housing width: 20 mm, Number of channels: 4-channel, 2:1 Method, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 4 x relay (NO contact), Reversible mode of operationpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Analog input (AI), Analog output (AO), Operates as transmitter power supply or current driver, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Analog input (AI), Analog output (AO), Operates as transmitter power supply or current driver, Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Analog input (AI), Analog output (AO), Operates as transmitter power supply or current driver, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA ... 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DCpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA ... 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, HART communication, Trip relay, Safety Integrity Level (SIL): SIL 2pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 3, Rated voltage: 19 ... 30 V DC, Signal: 1 x 4 ... 20 mApa
1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Type: 2-wire connection, Type [2]: 3-wire connection, Type [3]: 4-wire connectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Type: 2-wire connection, Type [2]: 3-wire connection, Type [3]: 4-wire connectionpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: resistance thermometer, Field device [2]: Thermocouplepa
1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: resistance thermometer, Field device [2]: Thermocouplepa
2-channel signal conditioner, 24 V DC supply, PNP/push-pull, dry contacts or NAMUR inputs, Selectable frequency trip values, 2 relay contact outputs, Start-up override, Selectable mode of operation, Without line fault detection, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Trip relay, Start-up override, Rotation direction monitoring, Rotation speed monitoring, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensorpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Redundant TC input, Current output 0/4 mA ... 20 mA, 2 relay contact outputs, Configurable by PACTware or keypad, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: resistance thermometerpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: 2-wire connection, Type [2]: 3-wire connection, Type [3]: 4-wire connectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: 2-wire connection, Type [2]: 3-wire connection, Type [3]: 4-wire connectionpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: 2-wire connectionpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: 2-wire connectionpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Strain gauge input (full or half bridge), Output 0 mA ... ± 20 mA or 0 V ... ± 10 V, 2 relay contact outputs, Programmable high/low alarm, Configurable by PACTware or keypad, RS-485 interface, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Rated voltage: 20 ... 35 V DC, Field device: strain gauge bridge, Type: 2 x relay (change-over contact), Signal: 1 x -20 ... 20 mApa
1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: resistance thermometer, Field device [2]: Thermocouplepa
1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: resistance thermometer, Field device [2]: Thermocouplepa
2-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DCpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Output 15.3 V DC at 17 mA, 3 logic inputs with AND/OR logic, Service port for isolator function test, Housing width: 20 mm, Number of channels: 1-channel, Rated voltage: 20 ... 30 V DC, Type: logic input, Field device: 1 x Valve, Current: typ. 18 mA, Voltage: typ. 16 Vpa
4-channel signal conditioner, 24 V DC supply (Power Rail), Output 600 mA per channel, Logic inputs, Common safety-oriented disable input, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 4-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Type: logic input, Field device: 4 x Valve, Field device [2]: 4 x audible alarm, Field device [3]: 4 x visual alarm, Line fault detection, Current: ≤ 600 mA, Voltage: typ. 23.8 Vpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/4 mA ... 20 mA, Terminals with test points, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 35 V DC, Field device: 2-wire transmitter, Signal: 0/4 ... 20 mA, Signal: 2 x 0/4 ... 20 mA (current source)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA, Terminal blocks with test sockets, High field voltage 17.6 V DC, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 35 V DCpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Scaleable current or voltage input, Current or voltage output, Relay contact output, Configurable by keypad, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 1-channel, Rated voltage: 20 ... 30 V DC, Type: 1 x relay (change-over contact), Signal: 1 x 0/4 ... 20 mA, Signal [2]: 1 x 0/1 ... 5 V, Signal [3]: 1 x 0/2 ... 10 V, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive), Application-specific outputs, Line fault transparency (LFT), Usable as signal splitter (1 input and 2 outputs), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive), Application-specific outputs, Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Level sensing input, Adjustable range 1 kΩ ... 150 kΩ, Relay contact output, Fault relay contact output, Adjustable time delay up to 10 s, Minimum/maximum control, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 1-channel, Conductivity measurement, Min./max. control, Time delay, Rated voltage: 20 ... 30 V DC, Signal: Resistance, Line fault detection, Type: 2 x relay (change-over contact), Fault indication outputpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Level sensing input, Adjustable range 1 kΩ ... 150 kΩ, Relay contact output, Adjustable time delay up to 10 s, Minimum/maximum control, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 2-channel, Conductivity measurement, Min./max. control, Time delay, Rated voltage: 20 ... 30 V DC, Signal: Resistance, Line fault detection, Type: 2 x relay (change-over contact), Fault indication outputpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Level sensing input, Adjustable range 1 kΩ ... 150 kΩ, Relay contact output, Fault relay contact output, Adjustable time delay up to 10 s, Minimum/maximum control, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 1-channel, Conductivity measurement, Min./max. control, Time delay, Rated voltage: 20 ... 30 V DC, Signal: Resistance, Line fault detection, Type: 2 x relay (change-over contact), Fault indication outputpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz ... 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Rotation speed monitoring, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz ... 12 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Rotation speed monitoring, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 35 V DC, Field device: 2-wire transmitterpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz ... 1 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Configurable by PACTware or keypad, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 2-channel, Trip relay, Start-up override, Frequency conversion, Rotation direction monitoring, Rotation speed monitoring, Synchronization monitoring, Slip monitoringpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Active transistor output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (active)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, TTL level, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operationpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive)pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive)pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Isolated passive transistor output, non-polarized, Isolated passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Selectable frequency trip values, 2 relay contact outputs, Start-up override, Selectable mode of operation, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Trip relay, Start-up override, Rotation direction monitoring, Rotation speed monitoring, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensorpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA, Terminals with test points, High field voltage 17.6 V DC, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 35 V DC, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitterpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for NAMUR sensors or dry contacts, Input frequency 1 mHz ... 5 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Frequency conversion, Rotation speed monitoring, Pulse divider, Safety Integrity Level (SIL): SIL 2pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz ... 1 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Configurable by PACTware or keypad, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 2-channel, Trip relay, Start-up override, Frequency conversion, Rotation direction monitoring, Rotation speed monitoring, Synchronization monitoring, Slip monitoringpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DCpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contactpa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 65 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC
loop powered, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 1 x Valvepa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC
loop powered, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 1 x Valvepa
Matching System Components
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of field and control signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.