General specifications |
Signal type | Analog input/analog output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Rated voltage | 10 ... 35 V DC , loop powered |
Power dissipation | 0.2 W |
Control circuit |
Connection | terminals 12-, 11+ |
Voltage | 10 ... 35 V DC |
Current | 4 ... 20 mA |
Power dissipation | < 150 mW per channel at 25 mA and U < 26.1 V < 400 mW per channel at 25 mA und U > 26.1 V |
Field circuit |
Connection | terminals 1+, 2- |
Voltage | ≥ 0.9 x Uin - (0.23 x current in mA) - 0.7 for 10 V < Uin < 26.1 V ≥ 23 V - (0.23 x current in mA) for Uin > 26.1 V |
Short-circuit current | max. 100 mA |
Transfer current | max. 25 mA |
Transfer characteristics |
Accuracy | 0.1 % |
Deviation | |
| After calibration | Uin ≥ 5 V ± 20 µA/Uin ≤ 5 V ± 50 µA incl. calibration, linearity, hysteresis and output load fluctuations at the field side; at 20 °C (68 °F) |
| Influence of ambient temperature | ≤ ± 2 µA/K at Uin ≤ 20 V; ≤ ± 5 µA/K at Uin > 20 V |
Rise time | ≤ 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V |
Galvanic isolation |
Input/Output | basic insulation according to IEC 62103, rated insulation voltage 300 Veff |
Indicators/settings |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | EN 61010-1:2010 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |