Standstill Monitor KFD2-SR2-2.W.SM

KFD2-SR2-2.W.SM
  • 1-channel standstill controller
  • Rotation direction detection or start-up override selectable
  • 2 relay outputs
  • Input frequency ≤ 2 kHz
  • Diagnosis LEDs for rotation detection, signal below the trip value, operating voltage and hardware error
  • Simple setting of function and limiting frequency via DIP switch on the front side
  • Plug-in terminals

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

將完整的規格書下載為PDF:


產品規格摘要:的技術資料  KFD2-SR2-2.W.SM

產品描述
1-channel
Supply
Connectionterminals 14+, 15-
Rated voltage20 ... 30 V DC
Power consumptionmax. 1.5 W
Input
ConnectionInput I: terminals 1+, 2+, 3- ;
Input II: terminals 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresisx ≤ 1.2 mA or x ≥ 2.1 mA / approx. 0.9 mA
Control inputsensor power supply approx. 8.2 V, impedance 1.2 kΩ
Line fault detectionnot available
Pulse duration> 200 µs for standstill monitoring,
> 250 µs for rotation direction detecion
Output
Connectionoutput I: terminals 7, 8, 9 ;
output II: terminals 10, 11, 12
Relay2 changeover contacts
Contact loading253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load;
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life5 x 106 switching cycles
Trip valuefor standstill monitoring:
0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz
adjustable via DIP switch (S1 and S2)
Transfer characteristics
Accuracy± 5 %
Start-up override5 seconds or 20 seconds, programmable
Frequency range≤ 2 kHz
Rotation direction detection90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connectionplug-in terminals
Massapprox. 150 g
Dimensions20 mm x 118 mm x 115 mm
Mountingsnap-on to 35 mm standard rail

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514