防爆產品服務資訊

AS-Interface analog module VBA-2E-G11-I/U/PT100-F

VBA-2E-G11-I/U/PT100-F
  • Addressing jack
  • Function display for bus, internal and external sensor power supply, inputs
  • Supply for inputs from AS-Interface or auxiliary voltage
  • Degree of protection IP68 / IP69K
  • Accuracy ± 0.1 %
  • Integrated shielding
  • Channel-specific input monitoring
  • Inputs for current, voltage or Pt100 temperature sensor

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

將完整的規格書下載為PDF:


產品規格摘要:的技術資料  VBA-2E-G11-I/U/PT100-F

產品描述
G11 analog module, 2 analog inputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.3.D
IO code7
ID code3
ID1 codeF
ID2 codeD
UL File NumberE223772
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
LED ANALOGstatus of input signal; LED yellow
off: not active
on: signal within measuring range
flashing: signal outside of measuring range
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INT/EXTstatus display input supply; LED green
green: input supply from AS-Interface
off: input supply from auxiliary voltage
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 60 mA (without sensors) / max. 200 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type2 analog inputs
Current: 0 ... 20 mA/4 ... 20 mA
voltage: 0 ... 10 V
Pt100: -200 ... 850 °C
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Current loading capacity≤ 140 mA from AS-Interface; overload and short-circuit resistant
≤ 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected
Input resistancecurrent input: max. 70 Ω
voltage input: 100 kΩ
Measuring currentfor Pt100: approx. 1 mA
AccuracyVoltage/current: 0.1% of accumulated value
Pt100: 0.1% of indicated temperature [°C] + 0.3 °C
Resolution16 Bit / 1 µA (current input) or
16 bit / 1 mV (voltage input) or
16 Bit / 0.1°C (temperature input)
Temperature influenceVoltage/current: 20 ppm/K
Pt100: (10 ppm of indicated temperature [°C] + 0.003 °C)/K
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black
Inputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
Dimensions
Height35 mm
Diameter85 mm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001596
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Details: VBA-2E-G11-I/U/PT100-F

Informative Literature: VBA-2E-G11-I/U/PT100-F

Language Selection:
Literature語言檔案類型檔案尺寸
Application Report - Automating Material Handling Systems for Airports with AS-InterfaceENGPDF272 KB

Product Documentation: VBA-2E-G11-I/U/PT100-F

Language Selection:
Brief Instructions語言檔案類型檔案尺寸
Instruction leaflet / BeipackzettelALLPDF679 KB
Manuals
Manual VBA-2E-G11-I/U/PT100-*ENGPDF2561 KB

Design / Simulation: VBA-2E-G11-I/U/PT100-F

Language Selection:
CAD語言檔案類型檔案尺寸
CAD 3-D / CAD 3-DALLSTP4756 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VBA-2E-G11-I/U/PT100-F

Language Selection:
Certificates證書號碼語言檔案類型檔案尺寸
Canada, USA ULCoC 20141115-E223772ALLPDF342 KB
EU Ecolab Material ResistanceECOLABALLPDF1797 KB
Worldwide AS-International Association AS-Interface94201ALLPDF376 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2931BALLPDF119 KB

相關產品: VBA-2E-G11-I/U/PT100-F

Accessories
Blind plug for M12 socketsfa
AS-Interface Handheld with accessoryfa
Adapter cable module/hand-held programming devicefa
Connecting cable, M12 to M12, PUR cable, 4-pin, bridged, shieldedfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

这份免费的 PDF 白皮书比较了不同的基于TCP标准的通信协议(包括 AMQP、OPC UA、MQTT、REST API),这些协议已成为 IIoT 和工业 4.0 的推动力。立即免费下载!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.