工業感測器服務資訊
+886 2 27227708
+886-2-27227782
防爆產品服務資訊

Voltage Repeater KFD2-VR2-Ex1.500M

KFD2-VR2-Ex1.500M
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Voltage input 0 mV ... ± 500 mV
  • Voltage output 0 mV ... ± 500 mV
  • Selectable up/downscale sensor breakage detection

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

將完整的規格書下載為PDF:


產品規格摘要:的技術資料  KFD2-VR2-Ex1.500M

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC
Ripplewithin the supply tolerance
Rated current≤ 11 mA
Power dissipation/power consumption0.3 W max.
Input
Connection sidefield side
Connectionterminals 4+, 5-
Input resistancemin. 20 MΩ
Transmission range-500 ... 500 mV
Offset voltage/current≤ 5 µV / ≤ 5 nA
Line fault detection1.3 µA
Output
Connection sidecontrol side
Connectionterminals 7+, 8-
Voltage-500 ... 500 mV
LoadAccuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ
Fault signalsensor breakage: > +500 mV (upscale), < -500 mV (downscale)
Output resistancemax. 3 Ω
Transfer characteristics
Cut-off frequency350 Hz (-3 dB)
Deviation
After calibrationat 20 °C (68 °F):
± 30 µV up to ± 100mV/± 0.03 % of the span up to +500 mV/± 0.03 % of the span up to -500 mV
Influence of ambient temperature± 10 µV/K (typical ± 5 µV/K)
Absolute< 0.25 K at 30 V voltage supply
Rise time≤ 1 ms
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 125 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0040
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Voltage5.5 V DC
Current2.4 mA
Power3.3 mW
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 09 ATEX 0219X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN 60079-11:2012
International approvals
UL approvalE106378
Control drawing116-0334 (cULus)
IECEx approval
IECEx certificateIECEx BAS 06.0011
IECEx BAS 09.0103X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210125
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-VR2-Ex1.500M

Informative Literature: KFD2-VR2-Ex1.500M

Language Selection:
Literature語言檔案類型檔案尺寸
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD2-VR2-Ex1.500M

Language Selection:
Safety and Security Documentation語言檔案類型檔案尺寸
Instruction manualENGPDF167 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-VR2-Ex1.500M

Language Selection:
CAD語言檔案類型檔案尺寸
CAD 3-D / CAD 3-DALLSTP2510 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ1161 KB

Approvals: KFD2-VR2-Ex1.500M

Language Selection:
Certificates證書號碼語言檔案類型檔案尺寸
Australia Test SafeANZEx 17.3006XALLPDF6788 KB
Baseefa IECEx Certificate of ConformityIECEx BAS 09.0103XALLLINK---
Baseefa IECEx Certificate of ConformityIECEx BAS 06.0011ALLLINK---
Brasil TUV Rheinland BrazilTÜV 13.1141ALLPDF1140 KB
Canada UL cULE106378 cUL (QUZW7)ALLLINK---
Canada UL cULE106378 cUL (QVAJ7)ALLLINK---
China SITIIAS CCC Ex Certificate2020322316001441 (Singapore)ALLPDF1069 KB
DNV MarineTAA00001WXALLPDF106 KB
Europe Baseefa II (1) D I (M1) II (1) GBaseefa 06 ATEX 0040ALLPDF269 KB
Europe Baseefa II 3 GBaseefa 09 ATEX 0219XALLPDF253 KB
USA ULE106378 UL (QUZW)ALLLINK---
USA ULE106378 UL (QVAJ)ALLLINK---
United Kingdom UKEX Category (1) G UK-Type Examination Certificate UKEX Category (M1) UKEX Category (1) DCML 21UKEX21101ALLPDF186 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF52 KB
Instruction leaflet / Beipackzettel   ALLPDF103 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0774DALLPDF83 KB

相關產品: KFD2-VR2-Ex1.500M

Matching System Components
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.