Surge Protector SCP-LBF-IA1.36.IE*

FieldConnex® Fieldbus
SCP-LBF-IA1.36.IE*
  • Pluggable, mounts between device coupler and spur cable
  • Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose
  • Optional diagnostics for wear
  • Grounding of shield via gas-discharge tube
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Indication via LED and Advanced Diagnostics

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

將完整的規格書下載為PDF:


產品規格摘要:的技術資料  SCP-LBF-IA1.36.IE*

產品描述
Surge protector, pluggable module for spur installation on segment protector
General specifications
Design / MountingCabinet installation
Installation in hazardous areaZone 1 / Div. 1
Fieldbus connection
Self current consumptionmax. 6 mA (for version SCP-LBF-IA1.36.IE.1) , max. 0 mA (for version SCP-LBF-IA1.36.IE.0)
Indicators/operating means
LED ERRgreen flashing: status OK , red flashing: maintenance required (for version SCP-LBF-IA1.36.IE.1)
Electrical specifications
Rated voltage36 V
Rated current250 mA
Voltage protection level
Line/Linemax. 50 V category B2 10/700 µsec , 25 A
max. 53 V category C1 8/20 µsec , 150 A
max. 55 V category C2 8/20 µsec , 150 A
max. 46 V category C3 1 kV/µsec , 10 A
Line/Earthmax. 980 V category B2 10/700 µsec , 50 A per line
max. 800 V category C1 8/20 µsec , 50 A per line
max. 1450 V category C2 8/20 µsec , 5 kA per line
max. 1200 V category C3 1 kV/µsec , 50 A per line
max. 980 V category D1 10/350 µsec , 500 A per line
Screen/Shield indirectly grounded (via GDT)max. 500 V category B2 10/700 µsec , 100 A
max. 600 V category C1 8/20 µsec , 500 A
max. 700 V category C2 8/20 µsec , 10 kA
max. 550 V category C3 1 kV/µsec , 100 A
max. 570 V category D1 10/350 µsec , 1 kA
Reaction time
Line/Linemax. 1 ns
Line/Earthmax. 100 ns
Screen/Shield-Earthmax. 100 ns
Overstressed fault modeaccording IEC 61643-21 line inoperable mode 2
Impulse durability
Per line5 kA category C2 8/20 µsec
Screen/Shield indirectly grounded (via GDT)1 kA category D1 10/350 µsec
10 kA category C2 8/20 µsec
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNAMUR NE 21
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Surge protectionIEC 61643-21
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typescrew terminals
Core cross sectionflexible wire 2.5 mm2 solid wire max. 4 mm2
Housing materialPolyamide PA 6.6
Degree of protectionIP20
Mass45 g
GroundingM4 screw and external grounding rail
Data for application in connection with hazardous areas
EU-type examination certificateSIRA 12 ATEX 2128X
MarkingEx-Hexagon II 1G Ex ia IIC T4
Voltage24 V
Current500 mA
Internal capacitance2 nF
Internal inductance0.1 µH
CertificateSIRA 12 ATEX 4176X
MarkingEx-Hexagon II 3G Ex nAc IIC T4 , Ex-Hexagon II 3G Ex ic IIC T4
Voltage33 V
Current600 mA
Internal capacitance2 nF
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007
Supplementary informationFISCO field device
International approvals
CSA approvalCoC 2595441
Control drawing116-0365
Approved forClass I, Division 1, Groups A, B, C, D T4
Class I, Zone 0, Ex ia IIC T4
Class I, Zone 2, Ex ic IIC T4
Class I, Zone 0, AEx ia IIC T4
Class I, Zone 2, AEx ic IIC T4
Class I, Division 2, Groups A, B, C, D T4
Class I, Zone 2, Ex nL IIC T4
Class I, Zone 2, Ex na IIC T4
Class I, Zone 2, AEx nAc IIC T4
IECEx approvalIECEx SIR 12.0051X
Approved forEx ia IIC T4
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.019170104
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC002584
ETIM 8.0EC002584
ETIM 7.0EC002584
ETIM 6.0EC002584
ETIM 5.0EC001604
UNSPSC 12.139121610

Details: SCP-LBF-IA1.36.IE*

Informative Literature: SCP-LBF-IA1.36.IE*

Language Selection:
Literature語言檔案類型檔案尺寸
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: SCP-LBF-IA1.36.IE*

Language Selection:
Safety and Security Documentation語言檔案類型檔案尺寸
Instruction manualENGPDF227 KB

Design / Simulation: SCP-LBF-IA1.36.IE*

Language Selection:
CAD語言檔案類型檔案尺寸
CAD 2-D / CAD 2-DALLZIP236 KB
CAD 3-D / CAD 3-DALLSTP2088 KB

Approvals: SCP-LBF-IA1.36.IE*

Language Selection:
Certificates證書號碼語言檔案類型檔案尺寸
Brasil TUV Rheinland BrazilTÜV 14.1589 XALLPDF1153 KB
Canada, USA CSA Ex i and Ex nCSA 13.2595441XALLPDF114 KB
China SITIIAS CCC Ex Certificate2020322304003528 (Singapore)ALLPDF1024 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe CSA ATEX Category 1 GSira 12 ATEX 2128XALLPDF215 KB
Europe CSA ATEX Category 3 G II 3 GSira 12 ATEX 4176XALLPDF228 KB
India PESO (India) CCOEA/P/HQ/KA/104/5866 (P506129)ALLPDF100 KB
Sira IECEx Certificate of ConformityIECEx SIR 12.0051XALLLINK---
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF92 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0814CENGENGPDF1142 KB

相關產品: SCP-LBF-IA1.36.IE*

Accessory of
FieldConnex® Fieldbus, Segment protector, junction box for fieldbus with short-circuit and fault protection, field junction box, electronic component for control cabinet installation, 4 ... 12 outputs Ex ic (FISCO or Entity) or non-incendive (Div 2), Advanced fault isolation at the spur, Segment Protector in Zone 2/Div. 2, Instruments in Zone 2/Div. 2 or Zone 1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, International, Europe, USA, Canadapa
FieldConnex® Fieldbus, Fieldbus barrier, module for DIN rail mounting, 8 ... 12 outputs Ex ia IIC, FISCO and Entity, Advanced fault isolation and diagnostics at the spur, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Device coupler location: Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa
Matching System Components
Segment Protector Junction Box, Brushed Stainless Steel, 4 ... 12 outputs Ex ic (FISCO or Entity), Brushed enclosure, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
4 ... 12 outputs Ex ic (FISCO or Entity), Glass fiber reinforced polyester, impact resistant, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk, Instrument location / spur protection: non-explosion hazardous area
Zone 2 - all relevant types of protection
Zone 1 - increased safetypa

Ethernet-APL 支持跨所有層級的連續通信。 了解有關開創性技術的更多信息……

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

從決策到規劃、安裝和調試再到操作和維護:了解如何充分利用您的現場總線基礎設施……