General specifications |
Design / Mounting | Motherboard based |
Installation in hazardous area | Zone 2 / Div. 2 |
Supply |
Rated voltage | 19.2 ... 35 V |
Rated current | 40 ... 25 mA |
Power dissipation | max. 1 W |
Fieldbus connection |
Number of segments | 4 |
Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA |
Rated voltage | 9 ... 32 V |
Indicators/operating means |
LED PRI PWR | green: on, primary bulk power supply connected |
LED SEC PWR | green: on, secondary bulk power supply connected |
LED Seg 1...4 | yellow: bus activity; yellow 2 Hz flashing: Maintenance required; red 2 Hz flashing: specification limit violated; red: hardware error |
Fault signal | VFC alarm 1 A, 50 V DC, normally closed |
DIP switch | fieldbus type , redundant supply , Signal level , Noise level , Jitter |
Galvanic isolation |
Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | < 95 % non-condensing |
Shock resistance | 15 g 11 ms |
Vibration resistance | 1 g , 10 ... 150 Hz |
Pollution degree | max. 2, according to IEC 60664 |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Core cross section | motherboard specific |
Housing material | Polycarbonate |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | |
| Height | 106 mm |
| Width | 18 mm |
| Depth | 128 mm |
Mounting | motherboard mounting |
Data for application in connection with hazardous areas |
Certificate | TÜV 04 ATEX 2500 X |
| Marking | II 3 G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval | |
| FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X |
| FM marking | Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex ec IIC T4 |
IECEx approval | |
| IECEx certificate | IECEx TUN 13.0038X |
| IECEx marking | Ex nA IIC T4 Gc |
Certificates and approvals |
Patents | This product may be covered by the following patent: US7,698,103 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |