Indicators/operating means |
LED PWR | LED green: flashing with short break (1 Hz) - IO-Link mode |
LED OL | overload of sensor power supply; LED red |
LED IO | Switching status/overload (input/output); 8 LED yellow/red yellow: input/output active red: output overload |
Electrical specifications |
Operating voltage | 18 ... 30 V DC, PELV
|
No-load supply current | max. 25 mA |
Operating current | max. 2 A |
Protection class | III |
Interface |
Interface type | IO-Link |
IO-Link revision | 1.1 |
Device profile | Identification and Diagnosis - I&D |
Process data | Inputs 2 Byte - Input signals 8 Bit - diagnosis signals 4 Bit Outputs 2 Byte - Output signals 8 Bit - Special functions 8 Bit |
Vendor ID | 1 (0x0001) |
Device ID | 984577 (0x0F0601) |
Data transfer rate | COM3 (230.4 kbits/s) |
Min. cycle time | 1 ms |
SIO mode support | no |
Compatible master port type | Class A , Class B |
Input |
Number/Type | 8 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO8) |
Supply | from IO-Link |
Voltage | 18 ... 30 V |
Current loading capacity | 400 mA , overload and short-circuit protected |
Input current | ≤ 5 mA (limited internally) |
Switching point | Type 1 according to IEC 61131-2 |
Output |
Number/Type | 8 electronic outputs, PNP (IO1 … IO8), overload proof and short-circuit proof |
Supply | from IO-Link |
Voltage | ≥ (UB - 1.5 V) |
Current | 200 mA per output |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 EN 55011:2016 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Fieldbus standard | EN 61131-9:2013 |
Input | EN 61131-2:2007 |
Communication interface | IEC 61131-9 / IO-Link V1.1.3 |
Emitted interference | EN 61000-6-4:2007 |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 |
Approvals and certificates |
UL approval | Protection class IP20 is not included in the UL approval. The protection class is tested by Pepperl+Fuchs. |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | 85 % non-condensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 5000 m above MSL |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz |
Pollution degree | 2 |
Mechanical specifications |
Degree of protection | IP20 according to EN 60529 |
Connection | 200 mm, PVC cable 0.5 mm2
|
Material | |
| Housing | Polyamide hot-melt adhesive |
Mass | 33 g |
Dimensions | |
| Height | 10 mm |
| Width | 36 mm |
| Length | 39.5 mm |
Note | This device is maintenance-free. If the device is used in a manner not specified by the manufaturer, the protection provided by the device may be impaired. |