Select Your Country
SJ3,5-S1N Inductive slot sensor
Key Benefits at a Glance
- 3.5 mm slot width
- Usable up to SIL 3 acc. to IEC 61508
- Nonferrous targets
Preferred Type







Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
CS
- CS
- DE
- EN
- ES
- FR
- IT
- PL
- PT
- SV
Technical data of SJ3,5-S1N
Switching function | Normally open (NO) | |
Output type | NAMUR with safety function | |
Slot width | 3.5 mm | |
Depth of immersion (lateral) | 5 ... 7 typ. 6 mm | |
Reference target | 10 x 7 x 0.3 mm3, Al | |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. | |
Output type | 2-wire |
Nominal voltage | Uo | 8.2 V (Ri approx. 1 kΩ) | ||||||
Switching frequency | f | 0 ... 2500 Hz | ||||||
Hysteresis | H | with NAMUR switch amplifier: 0.09 mm (e. g. Pepperl+Fuchs KCD2-SR-Ex1.LB) with safety switch amplifier 0.05 mm (e. g. Pepperl+Fuchs KFD2-SH-Ex1) | ||||||
Suitable for 2:1 technology | yes , with reverse polarity protection diode | |||||||
Rate of current rise | 2.1 mA / mm | |||||||
Current consumption | ||||||||
|
Safety Integrity Level (SIL) | SIL 3 | |
MTTFd | 11850 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % |
Standard conformity | ||||||||
|
IECEx approval | ||||||||||||||
| ||||||||||||||
ATEX approval | ||||||||||||||
| ||||||||||||||
UL approval | cULus Listed, General Purpose | |||||||||||||
| ||||||||||||||
CCC approval | ||||||||||||||
| ||||||||||||||
NEPSI approval | ||||||||||||||
|
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Connection type | flexible leads LiY | ||||||||||||||||
Housing material | PBT | ||||||||||||||||
Degree of protection | IP67 | ||||||||||||||||
Cable | |||||||||||||||||
| |||||||||||||||||
Dimensions | |||||||||||||||||
| |||||||||||||||||
Note | only for non-ferrous metal Adjustable stop |
Use in the hazardous area | see instruction manuals |