Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Hent hele databladet som PDF:
Uddrag af datablad: Tekniske data for
NRN15-18GS40-E2-IO
General specifications |
Switching function | Normally open/closed (NO/NC) programmable |
Output type | PNP |
Rated operating distance | 15 mm (factory setting) |
Near operating distance | 12 mm (can be activated by software) |
Installation | non-flush |
Output polarity | DC |
Assured operating distance | 0 ... 12.15 mm |
Reduction factor rAl | 1 |
Reduction factor rCu | 1 |
Reduction factor r304 | 1 |
Reduction factor rSt37 | 1 |
Output type | 3-wire |
Nominal ratings |
Operating voltage | 10 ... 30 V DC |
Switching frequency | 0 ... 550 Hz (switch point mode) 0 ... 50 Hz (window mode, switch point mode with stability alarm) |
Hysteresis | typ. 3 % |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | pulsing |
Voltage drop | ≤ 0.5 V |
Operating current | 0 ... 200 mA |
Off-state current | 0 ... 0.5 mA typ. 60 µA at 25 °C |
No-load supply current | ≤ 15 mA |
Time delay before availability | max. 150 ms |
Constant magnetic field | 200 mT |
Alternating magnetic field | 200 mT |
Status indicator | LED yellow |
Functional safety related parameters |
MTTFd | 362 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Interface |
Interface type | IO-Link ( via C/Q ) |
IO-Link revision | 1.1 |
Device ID | 0x201105 (2101509) |
Transfer rate | COM2 (38.4 kBit/s) |
Min. cycle time | 2.3 ms |
Process data width | Process data input (control system side): 2 Bit Process data output (control system side): none |
SIO mode support | yes |
Compatible master port type | A |
Compliance with standards and directives |
Standard conformity | |
| Standards | EN IEC 60947-5-2 |
Approvals and certificates |
Protection class | II |
| Rated insulation voltage | 60 V |
| Rated impulse withstand voltage | 800 V |
UL approval | cULus Listed, General Purpose Class 2 power source |
CCC approval | CCC approval / marking not required for products rated ≤36 V |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Mechanical specifications |
Connection type | cable PVC , 2 m |
Core cross section | 0.34 mm2 |
Housing material | Stainless steel 1.4305 / AISI 303 |
Sensing face | PBT |
Degree of protection | IP67 |
Cable | |
| Cable diameter | 4.3 mm ± 0.1 mm |
| Bending radius | > 15 x cable diameter |
Mass | 98 g |
Dimensions | |
| Length | 40 mm |
| Diameter | 18 mm |
Factory settings |
Default setting | operating mode = switch point mode with stability alarm switching function = Normally open (NO) switching distance = 15 mm |
General information |
Scope of delivery | 2 self locking nuts in scope of delivery |
Classifications
System | Classcode |
ECLASS 13.0 | 27274001 |
ECLASS 12.0 | 27274001 |
ECLASS 11.0 | 27270101 |
ECLASS 10.0.1 | 27270101 |
ECLASS 9.0 | 27270101 |
ECLASS 8.0 | 27270101 |
ECLASS 5.1 | 27270101 |
ETIM 9.0 | EC002714 |
ETIM 8.0 | EC002714 |
ETIM 7.0 | EC002714 |
ETIM 6.0 | EC002714 |
ETIM 5.0 | EC002714 |
UNSPSC 12.1 | 39121550 |
Details:
NRN15-18GS40-E2-IO
Product Documentation:
NRN15-18GS40-E2-IO
Design / Simulation:
NRN15-18GS40-E2-IO
Approvals:
NRN15-18GS40-E2-IO
Software:
NRN15-18GS40-E2-IO
Tilhørende produkter:
NRN15-18GS40-E2-IO
Accessories |
|
|
|
Mounting flange, 18 mm, Retainer for all cylindrical sensors with M18 thread, Simple installation and exact setting, Large sensing range (max. 20 mm)fa |
|
|
|
|
EtherNet/IP IO-Link master with 8 inputs/outputsfa |
|
|
|
|
PROFINET IO IO-Link master with 8 inputs/outputsfa |
|
|
|
|
EtherNet/IP IO-Link master with 8 inputs/outputs, DIN rail, screw terminalfa |
|
|
|
|
PROFINET IO IO-Link master with 8 inputs/outputs, DIN rail, push-in terminalsfa |
|
|
|
|
PROFINET IO IO-Link master with 8 inputs/outputs, DIN rail, screw terminalfa |
|
|
|
|
IO-Link master, supply via USB port or separate power supply, LED indicators, M12 plug for sensor connectionfa |
|
|
|
|
Ethernet IO-Link module with 8 inputs/outputsfa |
|
|
|
|
Ethernet IO-Link module with 8 inputs/outputsfa |
|
|
|
|
EtherNet/IP IO-Link master with 8 inputs/outputs, DIN rail, push-in connectorsfa |
|