Yhteydenotto, Koneautomaatio
+358 20 7861 290
Yhteydenotto, Prosessiautomaatio
+358 20 7861 291

Inductive sensor NEB6-12GM50-E3-Y70158977

NEB6-12GM50-E3-Y70158977
  • Increased operating distance
  • 6 mm flush

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Lataa koko tietolomake PDF-tiedostona:


Ote tietolomakkeesta: Tekniset tiedot  NEB6-12GM50-E3-Y70158977

General specifications
Switching functionNormally closed (NC)
Output typePNP
Rated operating distance6 mm
Installationquasi flush
Output polarityDC
Assured operating distance0 ... 4.8 mm
Actuating elementmild steel, e. g. 1.0037, SR235JR (formerly St37-2)
18 mm x 18 mm x 1 mm
Reduction factor rAl 0.28
Reduction factor rCu 0.2
Reduction factor r304 0.7
Reduction factor rBrass 0.35
Output type3-wire
Nominal ratings
Installation conditions
Ain steel 1.0037 (St37): 2.4 mm
in other metal: 1.2 mm
B12 mm
C18 mm
F24 mm
Operating voltage10 ... 30 V DC
Switching frequency0 ... 800 Hz
Hysteresis0.06 ... 1.2 mm
Reverse polarity protectionyes
Short-circuit protectionpulsing
Overload resistanceyes
Wire breakage protectionyes
Surge suppressionyes
Ripple10 %
Voltage drop≤ 2 V
Repeat accuracy0.3 mm
Operating current0 ... 200 mA , above 70°C max. 150 mA
Off-state current≤ 10 µA
No-load supply current≤ 15 mA
Time delay before availability≤ 50 ms
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1740 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN IEC 60947-5-2
Approvals and certificates
UL approvalcULus Recognized, Class 2 Power Source
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 85 °C (-13 ... 185 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typefixed cable with plug
Housing materialbrass, nickel-plated
Sensing facePBT
Degree of protectionIP67
ConnectorAMP connector
Number of pins3
Connection assemblyAMP housing 174359-2
AMP-Crimp 171631-1
AMP sealing 2822352-2
AMP Lock 1-174360-1
Cable
Cable diameter4.3 mm ± 0.1 mm
Bending radius> 10 x cable diameter
MaterialPUR
Colorblack
Number of cores3
Core cross section0.34 mm2
Length200 mm ± 10 mm
further length specifications: L1 = 20 mm
Dimensions
Length50 mm
Diameter12 mm

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NEB6-12GM50-E3-Y70158977

Design / Simulation: NEB6-12GM50-E3-Y70158977

Language Selection:
CADKieliTiedostotyyppiTiedoston koko
CAD 3-D / CAD 3-DALLSTP47 KB

Approvals: NEB6-12GM50-E3-Y70158977

Language Selection:
CertificatesSertifikaatin nroKieliTiedostotyyppiTiedoston koko
Canada USA UL Ordinary LocationUL-US-2013143-4 / UL-CA-2010423-4ALLPDF289 KB
China Information on CCCCCC-Exempt Declaration (Pepperl+Fuchs)ALLPDF457 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-7275_FINFINPDF1306 KB
UK Declaration of Conformity (P+F)TDOC-7276_ENGENGPDF1284 KB

Liitännäistuotteet: NEB6-12GM50-E3-Y70158977

Accessories

Mounting flange, 12 mmfa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.