General specifications |
Signal type | Analog output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 19 ... 30 V DC |
Ripple | ≤ 10 % |
Rated current | ≤ 30 mA |
Power dissipation | ≤ 600 mW |
Power consumption | ≤ 700 mW |
Input |
Connection side | control side |
Connection | terminals 5-, 6+ |
Input signal | 4 ... 20 mA limited to approx. 30 mA |
Input voltage | depending on switch configuration open loop voltage of the control system < 23 V open loop voltage of the control system < 27 V |
Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA |
Input resistance | > 100 kΩ, with field wiring open |
Output |
Connection side | field side |
Connection | terminals 1+, 2- |
Voltage | ≥ 13 V at 20 mA |
Current | 4 ... 20 mA |
Load | 0 ... 650 Ω |
Ripple | 20 mV rms |
Transfer characteristics |
Accuracy | 0.1 % |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ ± 0.1 % incl. non-linearity and hysteresis |
| Influence of ambient temperature | < 2 µA/K (0 ... 60 °C (32 ... 140 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F)) |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
Rise time | 10 to 90 % ≤ 100 ms |
Galvanic isolation |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LED |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |
| Height | 124 mm |
| Width | 12.5 mm |
| Length | 114 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | CESI 06 ATEX 021 |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I |
| Output | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Supply | |
| Maximum safe voltage | 250 V AC (Attention! Um is no rated voltage.) |
Equipment | terminals 1+, 2- |
| Voltage | 25.2 V |
| Current | 100 mA |
| Power | 630 mW |
| Internal capacitance | 5.7 nF |
| Internal inductance | negligible |
Certificate | PF 06 CERT 0973 X |
| Marking | II 3G Ex nA IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 116-0419 (cFMus) |
UL approval | |
| Control drawing | 116-0420 (cULus) |
IECEx approval | IECEx CES 06.0001 |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |