Supply | ||
---|---|---|
Connection | backplane LB9035A | |
Rated voltage | 24 V DC | |
Power consumption | max. 39 W , available output power for Zone 2 applications 5 W (5V), 20 W (12V), else 5 W (5V), 35 W (12V) | |
Auxiliary energy | 24 V DC Trunk load 10 mA according to FF standard. |
|
Redundancy | no | |
Fieldbus connection | ||
FOUNDATION Fieldbus | ||
Connection | plug-in screw connector on the backplane | |
Baud rate | 31.25 kBit/s , MBP | |
Protocol | H1 to IEC 1158-2 | |
Station connection | directly at the trunk or via spur protector | |
Number of stations per bus line | 1 or 2, depending on the required response times | |
Number of channels per station | max. 20 analog, max. 40 digital | |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) |
|
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) |
|
Addressing | via PCS (software) | |
Redundancy | no | |
Indicators/settings | ||
LED indication | Com unit LB8110*: LED green (power supply): on = operating, fast flash = cold start LED red (collective alarm): on = internal fault, flashing = no fieldbus LED yellow (operating mode): flashing = active Power supply LB9006C: LED green (power supply): off in case of loss of 24 V or 12 V or 5 V I/O modules (refer to the table with compatible modules for order codes): Power LED green: supply Diagnostic LED red: module fault, red flashing: communication error Status LED red: line fault Status LED yellow: signal (Live Zero status) |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
|
Mechanical specifications | ||
Degree of protection | IP20 | |
Dimensions | 275 x 127 mm (10.8 x 5 inch) | |
Data for application in connection with hazardous areas | ||
Certificate | PF 08 CERT 1234 X | |
Marking | II 3 G Ex nA IIC T4 | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0 , EN 60079-15 | |
General information | ||
System information | For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) an appropriate enclosure is required. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210119 |
ECLASS 12.0 | 27210119 |
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 9.0 | EC001598 |
ETIM 8.0 | EC001598 |
ETIM 7.0 | EC001598 |
ETIM 6.0 | EC001598 |
ETIM 5.0 | EC001598 |
UNSPSC 12.1 | 39121008 |
FF Modular I/O connects conventional field signals to FOUNDATION Fieldbus H1. It makes use of established reliable hardware and employs standard FF multi-function blocks. It supports NAMUR or switch type inputs as well as solenoid outputs, temperature signals or supply circuits for 2- or 4-wire transmitters, proportional valves and positioners. In contrast to dedicated digital input devices the FF Modular I/O combines analog and digital I/O in one device.
The modular approach enables a very compact solution, offering up to 40 digital, or 20 analog, or any combination of analog and digital inputs and outputs. The FF Modular I/O is installed locally near the instrumentation. The fieldbus cable serves as backbone. A selection of housing materials and accessories enables installation in Zone 2, Zone 22, Div. 2, or safe area.
Manuals | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Hardware Manual LB-Remote-I/O-System | ENG | 5385 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|