General specifications | ||
---|---|---|
Construction type | sensor: silicium sensor metall diaphragm |
|
Series | LHC-M51 | |
Supply | ||
Rated voltage | versions for safe area: 11.5 ... 45 V DC, 2-wire 11.5 ... 35 V DC, HART, 2-wire 9 ... 32 V DC, PROFIBUS PA version for hazardous area see safety information (SI) |
|
Input | ||
Measured variable | absolute or relative pressure | |
Measuring range | 0.4 ... 400 bar max. turn down: 100:1 |
|
Output | ||
Output signal | 4 ... 20 mA , analog , 2-wire 4 ... 20 mA with superimposed digital communication protocol HART 6.0, 2-wire digital communication signal PROFIBUS PA (Profile 3.02) |
|
Communication | 4 ... 20 mA HART (standard) PROFIBUS PA (option) |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 , EN 61326-2-5:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Measurement accuracy | ||
Accuracy | reference accuracy: ±0.15 % (standard), ±0.075 % (platinum) The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and non-reproducibility acc. to IEC 60770. The data refer to the calibrated span. |
|
Long-term drift | up to ±0.1 % of upper range limit (URL)/year | |
Operating conditions | ||
Process conditions | ||
Process temperature | -40 ... 125 °C (-40 ... 257 °F) hygienic versions: -40 ... 130 °C (-40 ... 266 °F), 150 °C/1h (302 °F/1h) |
|
Ambient conditions | ||
Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) with display : -20 ... 70 °C (-4 ... 158 °F) |
|
Mechanical specifications | ||
Degree of protection | IP66, NEMA 4X IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep) IP69K (with separate housing and FEP cable) |
|
Connection | gland M20 thread M20, G1/2, NPT1/2 device plug M12 HAN7D Harting connector, angled valve connector acc. ISO 4400, cable 5 m |
|
Material | materials in contact with process : 316L, Alloy C, rhodium>gold housing: - die-cast aluminum with protective powder-coating on polyester base, housing F31 - stainless steel AISI 316L (1.4404), housing F15 measuring cell seal: no, welded measuring cell |
|
Process connection | threads ISO 228: G1/2, G1, G1-1/2, G2 threads ANSI: NPT1/2, NPT1, NPT1-1/2, NPT2 hygienic process connections: Clamp, Varivent, DRD, DIN 11851, DIN 11864, NEUMO, APV, uni adapter flanges: EN 1092-1: DN 25 ... DN 80, ANSI 16.5: 1 ... 4 inch, JIS B2220 |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2009 | |
International approvals | ||
FM approval | see instruction manuals (SI) | |
CSA approval | see instruction manuals (SI) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
Drinking water approval | NSF61 approval | |
General information | ||
Supplementary documentation | technical information (TI) manuals, brief instructions (BA, KA) instruction manuals (SI) control drawings (ZD) approval (ZE) |
|
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Designation | see technical information (TI) |
System | Classcode |
---|---|
ECLASS 13.0 | 27200516 |
ECLASS 12.0 | 27200516 |
ECLASS 11.0 | 27200516 |
ECLASS 10.0.1 | 27200516 |
ECLASS 9.0 | 27200516 |
ECLASS 8.0 | 27200516 |
ECLASS 5.1 | 27200516 |
ETIM 9.0 | EC001447 |
ETIM 8.0 | EC001447 |
ETIM 7.0 | EC001447 |
ETIM 6.0 | EC001447 |
ETIM 5.0 | EC001447 |
UNSPSC 12.1 | 41111950 |
The device is used for absolute pressure and gauge pressure measurement in gases, steams or liquids.
The device has a piezoresistive measuring cell and a metallic welded process isolating diaphragm.
The operating pressure deflects the process isolating diaphragm. A fill fluid transfers the pressure to a resistance bridge (semiconductor technology). The pressure-dependent change in the bridge output voltage is measured and evaluated.
The data is transmitted to the control via analog signal, HART protocol or PROFIBUS PA.
The device is easily configured by the use of keypad or with the PACTware configuration software.
The device is designed modular and offers a variety of process connections, a replaceable display and a universal electronics.
Product information | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
TI00436O, Technical Information LHC, PPC | ENG | 8119 KB | |
Brief Instructions | |||
KA1030O, brief instructions LHC-M51, PPC-M51 4 mA ... 20 mA HART | ENG | 1633 KB | |
KA1031O, brief instructions LHC-M51, PPC-M51 PROFIBUS PA | ENG | 5215 KB | |
KA1036O, brief instructions LHC-M51, PPC-M51 4 mA ... 20 mA Analog | ENG | 802 KB | |
Safety and Security Documentation | |||
SI00466O, Instruction manual LHC-M51, PPC-M51 | ENG | 1246 KB | |
SI00469O, Instruction manual LHC-M51, PPC-M51 | ENG | 675 KB | |
SI00489O, Instruction manual LHC-M51, PPC-M51 | ENG | 836 KB | |
Safety Manual | ENG | 1293 KB | |
Safety Manual | ENG | 1268 KB | |
Manuals | |||
BA382O, Manual LHC-M51, PPC-M51 4 mA ... 20 mA HART | ENG | 2974 KB | |
BA383O, Manual LHC-M51, PPC-M51 PROFIBUS PA | ENG | 2820 KB | |
BA385O, Manual LHC-M51, PPC-M51 4 mA ... 20 mA Analog | ENG | 1512 KB |
CAD | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 1592 KB |
CAD 3-D additional / CAD 3-D additional | ALL | STP | 1312 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Device Description Files/Drivers | Julkaisutiedot | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
GSD / GSD | PF__0E3A.GSD | ZIP | 11 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|