Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Lataa koko tietolomake PDF-tiedostona:
Tuotekuvaus |
---|
Power feed module, redundant supply |
Supply | ||
---|---|---|
Connection | terminals 11+, 12- terminals 8+, 9- |
|
Rated voltage | 20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
|
Fusing | 5 AT/250 V AC recommended maximum utilization of the fuse: 80 % |
|
Power dissipation | ≤ 2.4 W | |
Output | ||
Connection | Power Rail | |
Output current | max. 4 A | |
Output voltage | Ui ≥ rated voltage Ur = Ui - 0.6 V | |
Fault signal | relay output: NO contact | |
Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
|
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | UL 22 ATEX 2853 X | |
Marking | II 3G Ex ec nC IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN IEC 60079-15:2019 | |
International approvals | ||
FM approval | FM 22 US 0031 X | |
Control drawing | 116-0160 | |
UL approval | E106378 | |
CSA approval | CoC 1051840 | |
IECEx approval | ||
IECEx certificate | IECEx UL 16.0051X | |
IECEx marking | Ex ec nC IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210119 |
ECLASS 12.0 | 27210119 |
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 9.0 | EC002653 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC002542 |
UNSPSC 12.1 | 39121004 |
The power feed module supplies the Power Rail with a voltage of 24 V DC and a maximum current of 4 A. The device is designed for applications requiring redundant power.
In the event of a device fault or a wiring fault of any isolator on the Power Rail, the collective error messaging relay alerts the controller via a binary I/O point. This relay can be configured as normally-open or normally-closed.
A green LED on the front of the device indicates the power state, and a red LED lights up during a fault condition.
Additionally, the bus implemented in the Power Rail is forwarded to the terminals 13 and 15 for usage with the RS-485 connection of the KFD2-WAC2-Ex1.D device. Terminal 14 is only for test purposes.
In the sense of functional safety (SIL) the device provides no dangerous failures. Thereby the safe condition of the supplied isolators must be defined as the de-energized state. Thus the device will not influence the safety calculation or the SIL value.
This device is compatible with all versions of the Power Rail and provides group fusing.
Note: Redundant systems require 2 KFD2-EB.R4A.B power feed modules.
Literature | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation Stage | ENG | 566 KB | |
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB |
Brief Instructions | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 79 KB | |
Safety and Security Documentation | |||
Käyttöohje | FIN | 155 KB | |
Manuals | |||
Manual | ENG | 3685 KB |
CAD | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2510 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
EPLAN macro EDZ / EPLAN Makro EDZ | ALL | EDZ | 59 KB |
Certificates | Sertifikaatin nro | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|---|
Canada CSA | CoC 1051840 C | ALL | 43 KB | |
China SITIIAS CCC Ex Certificate | 2024322303005906 (Vietnam) | ALL | 1864 KB | |
China SITIIAS CCC Ex Certificate | 2020322303003533 (Singapore) | ALL | 844 KB | |
DNV Marine | TAA00001WX | ALL | 106 KB | |
Europe UL ATEX Category 3 G | UL 22 ATEX 2853X | ALL | 23 KB | |
Korea KOSHA | 22-AV4BO-0058X | ALL | 67 KB | |
UL IECEx Certificate of Conformity | IECEx UL 16.0051X | ALL | LINK | --- |
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378 | CoC E106378 RepRef E106378-20160330 | ALL | 371 KB | |
USA FM | FM 22 US 0031X | ALL | 878 KB | |
Control Drawings | ||||
Control drawing FM / Control drawing FM | ALL | 146 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-0058DFIN | FIN | 174 KB | |
UKCA-Declaration of conformity / UKCA-Konformitätserklärung | DOC-5299A | ALL | 96 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
Matching System Components | ||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|