Sélectionnez votre pays

Accéder au site Web mondial

R2-SP-IC* Segment ProtectorFieldConnex® Fieldbus

Principaux avantages en un coup d'œil

  • 4 ... 12 outputs Ex ic (FISCO or Entity) or non-incendive (Div 2)
  • Advanced fault isolation at the spur
  • Segment Protector in Zone 2/Div. 2
  • Instruments in Zone 2/Div. 2 or Zone 1/Div. 1
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Advanced Diagnostics at the spur
  • Power, Com, Diagnostics, and Error LEDs
  • T-connector for easy installation and maintenance
  • Test points for easy troubleshooting

Afficher plus

FieldConnex® interface
Product Compliance: Europe – CE
FOUNDATION Fieldbus interface
Approval
PROFIBUS interface
Interface
Remarque

Tous les documents relatifs aux produits, tels que les certificats, les déclarations de conformité, etc., qui ont été émis avant la conversion sous le nom de Pepperl+Fuchs GmbH ou Pepperl+Fuchs AG, s'appliquent également à Pepperl+Fuchs SE.

DE
  • DE
  • EN

Données techniques relatives à R2-SP-IC*

Segment protector, junction box for fieldbus with short-circuit and fault protection, field junction box, electronic component for control cabinet installation
Design / MountingCabinet installation
Installation in hazardous areaZone 2 / Div. 2
Main cable (Trunk)
Rated voltage9 ... 31 V DC
10.5 V DC minimum input voltage acc. to FF-846
Rated currentmax. 4.5 A
Outputs
Number of outputssee table "Technical data depending on model"
Number of devices per output1
Rated voltagemax. 31 V
Rated currentmax. 32 mA switch 1, position 1
max. 43 mA switch 1, position 2
Short-circuit current46 mA switch 1, position 1
57 mA switch 1, position 2
Self current consumptionsee table "Technical data depending on model"
Voltage drop main cable/outputsmax. 1.2 V
Voltage drop trunk In/Out0 V
Terminating resistorexternal type M-FT 100 Ω +/- 10 %
Surge protectionTrunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Switchconfiguration of short-circuit current/rated current
LED PWRgreen: Fieldbus voltage > 10 V and fieldbus terminator is deactivated
LED COM/ERRyellow: flashing: fieldbus communication status and physical layer diagnostic status
LED SPURSred: 2 Hz flashing in short-circuit condition
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient temperature-50 ... 70 °C (-58 ... 158 °F)
Storage temperature-50 ... 85 °C (-58 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Connection typescrew terminal , pluggable or spring terminal , pluggable
Core cross sectionsee table 2
Housing materialPolycarbonate
Degree of protectionIP20
Masssee table "Technical data depending on model"
Dimensionssee table "Technical data depending on model"
MountingDIN rail mounting
EU-type examination certificateTÜV 12 ATEX 098651 X
MarkingEx-Hexagon II 3G Ex nA [ic] IIC T4 Gc
[exsign] II (3)D [Ex ic Dc] IIIC
Supply
Maximum safe voltageUm35 V
Outputs
VoltageUo32 V
CurrentIo46 mA switch 1, position 1
65 mA switch 1, position 2
InductanceLo0.125 mH switch 1, position 1
0.25 mH switch 1, position 2
CapacitanceCo60 nF
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
UL approvalE106378
Control drawing116-0406
Approved forClass I, Division 2, Groups A, B, C, D
IECEx approval
IECEx certificateIECEx TUN 12.0015X
IECEx markingEx nA [ic] IIC T4 Gc
[Ex ic Dc] IIIC
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Notes générales