Supply |
Connection | backplane bus |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
Nominal voltage | 12 V DC , |
Power dissipation | 4.53 W |
Power consumption | 4.53 W |
Fieldbus connection |
Fieldbus type | PROFINET |
Ethernet Interface |
Connection type | RJ-45 , via front connector |
Transfer rate | 10BASE-T, 100BASE-TX 100 MBit/s |
Station connection | directly to PCS or PLC or via hubs or switches |
Cable type | SFTP in accordance with ISO/IEC 11801 for Cat 5e or better |
Bus length | max. 100 m per link |
Addressing | DHCP, via controller (DCP) or fixed IP address |
Ethernet address | IP V4 address (preset: DHCP on, changeable via display) |
Supported I/O modules | LB1x01*…LB1x03*, LB1x08*, LB1x09*, LB2x01*…LB2x17*, LB3x01*…LB3x06*, LB4x01*, LB4x02*, LB4x04*…LB4x06*, LB5x01*, LB5x02*, LB5x04*…LB5x06*, LB6x01*, LB6x05*, LB6x06*, LB6x08*, LB6x10*…LB6x17*, LB7x04* |
HART communication | via PROFINET and HART I/P |
PROFINET conformance class | CC B |
Internal bus |
Connection | backplane bus |
Galvanic isolation |
Ethernet/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC |
RS 485 interface/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC |
Insulation voltage | 1500 V AC acc. to IEEE 802.3u |
Electrical isolation |
Power supply, internal bus/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1 |
Conformity |
Degree of protection | IEC 60529 |
Fieldbus standard | IEEE 802.3 |
Environmental test | EN 60068-2-14 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Damaging gas | EN 60068-2-42 |
Relative humidity | EN 60068-2-56 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 (module) , mounted on backplane |
Connection | via backplane |
Mass | approx. 150 g |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
Data for application in connection with hazardous areas |
Certificate | DEMKO 16 ATEX 1780 X |
| Marking | II 3 G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 EN 60079-15:2010
|
International approvals |
ATEX approval | DEMKO 16 ATEX 1780 X |
IECEx approval | IECEx UL 16.0141 X |
| Approved for | Ex nA IIC T4 Gc |
General information |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |