Assistance gamme Détecteurs industriels
Support en ligne pour la protection contre le risque d’explosion

Segment Protector Junction Box, Polyester (GRP) F.SPE.P**.A**.1.0.***.***.****

F.SPE.P**.A**.1.0.***.***.****
  • Connection of Ex d certified devices
  • Glass fiber reinforced polyester, impact resistant, IP66
  • Configurable cable entries for trunk and spurs
  • International approvals
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 1

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Téléchargez ici la fiche technique complète en PDF:


Caractéristiques techniques  F.SPE.P**.A**.1.0.***.***.****

General specifications
Design / MountingOutside installation
Installed componentsSegment Protector R-SP-E12
For technical data on installed electronic component see data sheet.
Conformity
Degree of protectionEN 60529
Impact resistanceEN 60079-0
Ambient conditions
Ambient temperature-30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Impact resistance7J
Mechanical specifications
Enclosure coverdetachable cover with retaining screws
Degree of protectionIP66
Cable entrycable gland and stopping plug options see separate table
Material
Housingpolyester , impact resistant, glass fiber reinforced
Surfaceblack molded finish (RAL 9005)
Surface resistance< 109 Ω
Water absorption< 6 %
Sealsilicone , one-piece
Grounding platebrass
Material thicknessgrounding plate: 3 mm
Dimensions(W x H x D)
271 x 271 x 136 mm (1 x R2-SP-E12)
544 x 271 x 136 mm (2 x R2-SP-E12)
Mountingthru-holes Ø6.5 mm
Groundinggrounding bolt M6 , Stainless steel
Data for application in connection with hazardous areas
EU-type examination certificatePTB 07 ATEX 1061 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II 2G Ex db eb mb IIC T4 Gb
Ex-Hexagon II 2D Ex tb IIIC T135°C Db
Note: The marking is based on the maximum value and can be reduced depending on the selected options accordingly.
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-1:2007 , EN 60079-7:2015 , EN 60079-18:2009 , EN 60079-31:2014
International approvals
IECEx approvalIECEx PTB 07.0036 X , suitable Junction Box on request
INMETRO approvalTÜV 13.1143
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: F.SPE.P**.A**.1.0.***.***.****

Informative Literature: F.SPE.P**.A**.1.0.***.***.****

Language Selection:
LiteratureLangueType de fichierTaille
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F.SPE.P**.A**.1.0.***.***.****

Language Selection:
Safety and Security DocumentationLangueType de fichierTaille
Manuel d'instructionsFRAPDF154 KB
Manuals
ManualENGPDF967 KB

Approvals: F.SPE.P**.A**.1.0.***.***.****

Language Selection:
CertificatesIdentificationLangueType de fichierTaille
Brasil TUV Rheinland BrazilTÜV 13.1143ALLPDF1259 KB
Europe PTB ATEX Category 2 G ATEX Category 2 DPTB 07 ATEX 1061 XALLPDF500 KB
Worldwide PTB IECEx Certificate of Conformity CertificateIECEx PTB 07.0036XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3149CALLPDF132 KB

Produits associés : F.SPE.P**.A**.1.0.***.***.****

Matching System Components
FieldConnex® Fieldbus, Segment protector, junction box for fieldbus with short-circuit protection, Field junction box, module for DIN rail mounting, 12 increased safety outputs (Ex e), Short circuit current limitation per output, Segment Protector in Zone 1/Div. 2, Instruments in Zone 1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Europe, Device coupler location: Zone 1 - high-power trunk, Instrument location / spur protection: Zone 1 - increased safetypa

Ethernet-APL assure une communication continue à tous les niveaux hiérarchiques. En savoir plus sur cette technologie pionnière…

Mises à jour RSS Info Service pour PANOS

Soyez informé dès qu'une nouvelle mise à jour logicielle de PANOS, le système d'exploitation des commutateurs Ethernet-APL, est disponible : Grâce à notre flux RSS vous serez immédiatement informé par e-mail de la publication d'une mise à jour.

De la prise de décisions à la planification, en passant par l'installation et la mise en service, sans oublier l'exploitation et la maintenance : Découvrez comment tirer le meilleur parti de votre infrastructure de bus de terrain…