Description produit |
---|
Advanced diagnostic module with relay output for fieldbus power hub physical layer diagnostics |
General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Rated voltage | 19.2 ... 35 V | |
Rated current | 40 ... 25 mA | |
Power dissipation | max. 1 W | |
Fieldbus connection | ||
Number of segments | 4 | |
Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA | |
Rated voltage | 9 ... 32 V | |
Indicators/operating means | ||
LED PRI PWR | green: on, primary bulk power supply connected | |
LED SEC PWR | green: on, secondary bulk power supply connected | |
LED Seg 1...4 | yellow: bus activity; yellow 2 Hz flashing: Maintenance required; red 2 Hz flashing: specification limit violated; red: hardware error | |
Fault signal | VFC alarm 1 A, 50 V DC, normally closed | |
DIP switch | fieldbus type , redundant supply , Signal level , Noise level , Jitter | |
Galvanic isolation | ||
Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Core cross section | motherboard specific | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | ||
Height | 106 mm | |
Width | 18 mm | |
Depth | 128 mm | |
Mounting | motherboard mounting | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 04 ATEX 2500 X | |
Marking | II 3 G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X | |
FM marking | AEx/Ex ec IIC T4 | |
IECEx approval | ||
IECEx certificate | IECEx TUN 13.0038X | |
IECEx marking | Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
Patents | This product may be covered by the following patent: US7,698,103 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 27242692 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC001604 |
ETIM 8.0 | EC001604 |
ETIM 7.0 | EC001604 |
ETIM 6.0 | EC001604 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Literature | Langue | Type de fichier | Taille |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB | |
Application Report - Fieldbus Power Supply Compatible with Process Industry Applications | ENG | 229 KB |
Safety and Security Documentation | Langue | Type de fichier | Taille |
---|---|---|---|
Manuel d'instructions | FRA | 221 KB | |
Manuals | |||
Manual HD2-DM-A.RO Advanced Diagnostic Module Relais Output | ENG | 767 KB |
Certificates | Identification | Langue | Type de fichier | Taille |
---|---|---|---|---|
Canada FM | FM 19 CA 0011X | ALL | 356 KB | |
China SITIIAS CCC | 2020322310003510 (Singapore) | ALL | 1330 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe TUV Nord ATEX Category 3 G | TÜV 04 ATEX 2500X | ALL | 1498 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5874 (P507650) | ALL | 101 KB | |
USA FM | FM 19 US 0015X | ALL | 213 KB | |
Worldwide TUV Nord Ex nA nC IECEx nA | IECEx TUN 13.0038X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0756C | ALL | 1040 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
Matching System Components | ||||||
|
Mises à jour RSS Info Service pour PANOS
Soyez informé dès qu'une nouvelle mise à jour logicielle de PANOS, le système d'exploitation des commutateurs Ethernet-APL, est disponible : Grâce à notre flux RSS vous serez immédiatement informé par e-mail de la publication d'une mise à jour.