Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Téléchargez ici la fiche technique complète en PDF ::
Description produit |
---|
Fieldbus power supply with low voltage for compact plants also in island mode |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Connection | Power Rail or terminals 8+, 11+; 9-, 12- | |
Rated voltage | 10 ... 30 V DC | |
Rated current | 350 ... 120 mA | |
Power dissipation | typ. ≤ 0.5 W | |
Fieldbus connection | ||
Number of segments | 1 | |
Connection | terminals 3+, 6+; 2-, 5-; 1S, 4S (S=screen connection) | |
Rated voltage | 12 ... 13 V | |
Rated current | 220 mA | |
Galvanic isolation | ||
Fieldbus segment/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 250 V AC | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2, ISA S 50.02 part 2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminal , pluggable | |
Core cross section | up to 2.5 mm2 | |
Housing | 20 mm x 115 mm x 107 mm | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 210 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 06 ATEX 553079 X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 | |
International approvals | ||
FM approval | ||
FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X | |
FM marking | AEx/Ex ec IIC T4 | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242611 |
ECLASS 12.0 | 27242611 |
ECLASS 11.0 | 27242611 |
ECLASS 10.0.1 | 27242611 |
ECLASS 9.0 | 27242611 |
ECLASS 8.0 | 27242611 |
ECLASS 5.1 | 27242611 |
ETIM 9.0 | EC002583 |
ETIM 8.0 | EC002583 |
ETIM 7.0 | EC002583 |
ETIM 6.0 | EC002583 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121004 |
Literature | Langue | Type de fichier | Taille |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Langue | Type de fichier | Taille |
---|---|---|---|
Manuel d'instructions | FRA | 62 KB |
Certificates | Identification | Langue | Type de fichier | Taille |
---|---|---|---|---|
Canada FM | FM 19 CA 0011X | ALL | 356 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe TUV Nord ATEX II 3 G | TÜV 06 ATEX 553079X | ALL | 2011 KB | |
USA FM | FM 19 US 0015X | ALL | 213 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2718B | ALL | 1039 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
Mises à jour RSS Info Service pour PANOS
Soyez informé dès qu'une nouvelle mise à jour logicielle de PANOS, le système d'exploitation des commutateurs Ethernet-APL, est disponible : Grâce à notre flux RSS vous serez immédiatement informé par e-mail de la publication d'une mise à jour.