Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Téléchargez ici la fiche technique complète en PDF ::
Description produit |
---|
Power hub motherboard for Yokogawa ALF111 |
General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Connection | redundant | |
Rated voltage | 19.2 ... 35 V SELV/PELV | |
Rated current | 16 A | |
Power dissipation | typ. 0.4 W per segment | |
Fieldbus connection | ||
Number of segments | 8 Redundant Power Supply | |
Host-side | redundant Yokogawa ALF111 with AKB336 interface cables | |
Terminating resistor | 100 Ω integrated | |
Indicators/operating means | ||
Fault signal | VFC alarm 1 A, 50 V DC, normally closed | |
Galvanic isolation | ||
Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Fieldbus segment/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminal , pluggable spring terminal , pluggable |
|
Core cross section | 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 1350 g | |
Dimensions | ||
Height | 150 mm | |
Width | 268 mm | |
Depth | 69 mm | |
Mounting | DIN mounting rail | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 10 ATEX 555761X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-7:2015 | |
International approvals | ||
FM approval | FM19US0015X FM19CA0011X | |
Approved for | Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex ec IIC T4 | |
IECEx approval | IECEx TUN 13.0037X | |
Approved for | Ex ec IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV TAA 0000272 , pending for MBHC-FB-8R.YO.R | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242603 |
ECLASS 12.0 | 27242603 |
ECLASS 11.0 | 27242603 |
ECLASS 10.0.1 | 27242603 |
ECLASS 9.0 | 27242603 |
ECLASS 8.0 | 27242603 |
ECLASS 5.1 | 27242603 |
ETIM 9.0 | EC001598 |
ETIM 8.0 | EC001598 |
ETIM 7.0 | EC001598 |
ETIM 6.0 | EC001598 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Literature | Langue | Type de fichier | Taille |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB | |
Application Report - Fieldbus Power Supply Compatible with Process Industry Applications | ENG | 229 KB | |
Guideline for Using Fieldbus Equipment in Zone 2 | ENG | 830 KB |
System Descriptions | Langue | Type de fichier | Taille |
---|---|---|---|
Conformity matrix for R2-SP-IC* and F2-SP-IC* with motherboards: MBHC*, FBTA-228-BPFB-R-8R and power supply modules: HCD2-FBPS-* | ENG | 143 KB | |
Safety and Security Documentation | |||
Manuel d'instructions | FRA | 235 KB | |
Manuals | |||
Manual | ENG | 1882 KB |
CAD | Langue | Type de fichier | Taille |
---|---|---|---|
CAD 2-D / CAD 2-D | ALL | ZIP | 3914 KB |
Certificates | Identification | Langue | Type de fichier | Taille |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 14.0356 X | ALL | 1118 KB | |
Canada FM | FM 19 CA 0011X | ALL | 356 KB | |
China SITIIAS CCC Ex Certificate | 2020322303003509 (Singapore) | ALL | 1406 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe TUV Nord ATEX Category 3 G | TÜV 10 ATEX 555761X | ALL | 2296 KB | |
TUV Nord IECEx ec Certificate of Conformity | IECEx TUN 13.0037X | ALL | LINK | --- |
USA FM | FM 19 US 0015X | ALL | 213 KB | |
Worldwide Fieldbus Foundation | PS066300 | ALL | 31 KB | |
Worldwide Fieldbus Foundation | PS066200 | ALL | 31 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-2261EFRA | FRA | 1141 KB |
Variants | ||||||
---|---|---|---|---|---|---|
|
||||||
Matching System Components | ||||||
|
||||||
|
Mises à jour RSS Info Service pour PANOS
Soyez informé dès qu'une nouvelle mise à jour logicielle de PANOS, le système d'exploitation des commutateurs Ethernet-APL, est disponible : Grâce à notre flux RSS vous serez immédiatement informé par e-mail de la publication d'une mise à jour.