请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。
產品規格摘要:的技術資料
NJ5-18GM-N
General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 5 mm |
Installation | flush |
Assured operating distance | 0 ... 4.05 mm |
Reduction factor rAl | 0.21 |
Reduction factor rCu | 0.18 |
Reduction factor r304 | 0.63 |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Operating voltage | 5 ... 25 V |
Switching frequency | 0 ... 500 Hz |
Hysteresis | 3 % |
Current consumption | |
| Measuring plate not detected | ≥ 3 mA at nominal voltage |
| Measuring plate detected | ≤ 1 mA at nominal voltage |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
MTTFd | 4566 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standards | EN IEC 60947-5-2 |
Approvals and certificates |
IECEx approval | |
| Equipment protection level Ga | IECEx PTB 11.0037X |
| Equipment protection level Gb | IECEx PTB 11.0037X |
| Equipment protection level Da | IECEx PTB 11.0037X |
| Equipment protection level Mb | IECEx PTB 11.0037X |
ATEX approval | |
| Equipment protection level Ga | PTB 00 ATEX 2048 X |
| Equipment protection level Gb | PTB 00 ATEX 2048 X |
| Equipment protection level Da | PTB 00 ATEX 2048 X |
UL approval | |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0452 |
CCC approval | |
| Hazardous Location | 2020322315002255 |
CML approval | on request |
ANZEx | 18.3018X |
KCC approval | |
| Hazardous Location | 19-AV4BO-0227 |
Marine approval | DNVGL TAA00001A5 |
Ambient conditions |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications |
Connection type | cable |
Housing material | Stainless steel 1.4305 / AISI 303 |
Sensing face | PBT |
Degree of protection | IP66 / IP67 |
Cable | |
| Cable diameter | 6 mm ± 0.2 mm |
| Bending radius | > 10 x cable diameter |
| Material | PVC |
| Core cross section | 0.75 mm2 |
| Length | 2 m |
Dimensions | |
| Length | 40 mm |
| Diameter | 18 mm |
General information |
Use in the hazardous area | see instruction manuals |
Classifications
System | Classcode |
ECLASS 13.0 | 27274001 |
ECLASS 12.0 | 27274001 |
ECLASS 11.0 | 27270101 |
ECLASS 10.0.1 | 27270101 |
ECLASS 9.0 | 27270101 |
ECLASS 8.0 | 27270101 |
ECLASS 5.1 | 27270101 |
ETIM 9.0 | EC002714 |
ETIM 8.0 | EC002714 |
ETIM 7.0 | EC002714 |
ETIM 6.0 | EC002714 |
ETIM 5.0 | EC002714 |
UNSPSC 12.1 | 39121550 |
Details:
NJ5-18GM-N
Product Documentation:
NJ5-18GM-N
Design / Simulation:
NJ5-18GM-N
相關產品:
NJ5-18GM-N
Accessories |
|
|
|
Mounting flange, 18 mm, Retainer for all cylindrical sensors with M18 thread, Simple installation and exact setting, Large sensing range (max. 20 mm)fa |
|