IO-Link converter ICA-AO-I/U-IO-V1

ICA-AO-I/U-IO-V1
  • IO-Link interface
  • IP67
  • Analog output cab be parameterized (current/voltage)
  • Current output can be parameterized as 0 … 20 mA/4 … 20 mA
  • Voltage output can be parameterized as -10 … 10 V/0 … 10 V

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICA-AO-I/U-IO-V1

Product Description
IO-Link converter with analog output (current/voltage)
General specifications
UL File NumberE223772
Functional safety related parameters
MTTFd246 a
Indicators/operating means
LED 1Device status, diagnostics
LED 2IO-Link status
Electrical specifications
Rated operating voltage18 ... 30 V
Nominal voltage24 V DC
Nominal current230 mA
Current consumptiontyp. 30 mA
Surge protectionCategory II
Interface
Interface typeIO-Link
IO-Link revision1.1
Device ID0x0F0502 (984322)
Transfer rateCOM2 (38.4 kBit/s)
Min. cycle time2.3 ms
Process data width16 bits / 2 bytes
SIO mode supportno
Compatible master port typeA, B
Output
Number/Type1 analog output for actuators with analog input
ResolutionADC: 24 bit
Process data: 16 bit
Accuracy0.1 % FS at 25 °C
Measuring rangeCurrent output or voltage output, configurable:
0 mA…20 mA
4 mA…20 mA
0 V…10 V
-10 V…10 V
Sensor supply17 … 29.8 V DC
≤ 200 mA
Output filterAverage determination of process data, parameterizable
Temperature influence45 ppm/°K
Sampling ratemax. 200 Hz
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardIEC 61131-9 / IO-Link V1.1
Emitted interferenceEN 61000-6-4
Noise immunityEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-6
Shock resistanceEN 60068, Part 2-6, Part 2-27
Ambient conditions
Ambient temperature-30 ... 70 °C (-22 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 85 %
Climatic conditionsClimatic class 3K3
Altitude0 ... 2000 m
Shock and impact resistance50 g, 11 ms, all axes
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionIO-Link M12, A-coded
Input M12, A-coded
Material
ContactsZinc, CuNi plated
HousingPlastic PC + PBT
Mass44 g
Dimensions
Height32.3 mm
Width16 mm
Length79.7 mm
Construction typeField housing

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-AO-I/U-IO-V1

Product Documentation: ICA-AO-I/U-IO-V1

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manual / BetriebsanleitungALLPDF4483 KB
Manuals
Manual ICA-AI-I/U-IO-V1 and ICA-AO-I/U-IO-V1ENGPDF2677 KB
Parameter Information
Parameterdatenblatt / Parameter DatasheetENGPDF392 KB

Approvals: ICA-AO-I/U-IO-V1

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
IO-Link Manufacturer DeclarationCERT-6084AALLPDF174 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-5028CENGENGPDF339 KB

Software: ICA-AO-I/U-IO-V1

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
IODD for ICA-AO-I/U-IO / IODD für ICA-AO-I/U-IOV1.01.000 / 2023-12-14ZIP159 KB

Associated Products: ICA-AO-I/U-IO-V1

Accessories
85.00  USD
Netlist price. Your individual price will be calculated during checkout.

In stock

torque screwdriver (0.6 Nm)fa
77.00  USD
Netlist price. Your individual price will be calculated during checkout.

In stock

plug-in cap M12fa
420.00  USD

Contact Us

IO-Link master, supply via USB port or separate power supply, LED indicators, M12 plug for sensor connectionfa
IIoT Starter Kit

Connect your factory floor sensors to the cloud and start your digital transformation with the new IIoT starter kits.