Your technical, product, or application questions answered in one business day* by our team of experts.
! Please fill in all fields before submitting your question. Pepperl+Fuchs values your privacy. Please read our privacy policy.
* Pepperl+Fuchs makes every effort to provide an answer that is helpful and relevant to you. Your question is typically answered in one business day. Occasionally, an answer is delayed. In these cases, we are often researching your question, conferring with colleagues, or may route your question to another Pepperl+Fuchs location. You will be notified via e-mail regarding the status of your question.
Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Datasheet excerpt: Technical data of
ICE1-8IOL-S2-G60L-V1D
Product Description
Ethernet IO-Link master with PROFINET S2 redundancy
General specifications
UL File Number
E223772
Functional safety related parameters
MTTF
582 a
Indicators/operating means
LED indication
see manual
Rotary switch
Setting the fieldbus protocol
Electrical specifications
Rated operating voltage
18 ... 30 V
Nominal voltage
24 V DC
Current consumption
typ. 200 mA
Current loading capacity
Max. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 9 A per module
Galvanic isolation
between US and UL
Interface 1
Interface type
Industrial Ethernet
Physical
M12, D-coded
Protocol
PROFINET IO with media redundancy protocol (MRP) and S2 system redundancy. EtherNet/IP with Device Level Ring (DLR)
Transfer rate
10/100 Mbps
Inputs/Outputs
Number/Type
4 x IO-Link Class A (X1 – X4) 4 x IO-Link Class B (X5 – X8) Configurable as: max. 8 IO-Link and 4 digital inputs and outputs max. 12 digital inputs and 4 digital outputs max. 12 digital outputs and 4 digital inputs short-circuit protected
Sensor supply
max. 500 mA per port (X1 - X8) via L+ (pin 1)
Output current
max. 500 mA per port (X1 - X8) Via C/Q (pin 4) In addition, a maximum of 2 A per port (X5 – X8) Via UAux (pin 2)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU
EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Standard conformity
Degree of protection
EN 60529:2000
Fieldbus standard
Type 1 according to IEC 61131-2
Emitted interference
EN 61000-6-4:2007+A1:2011
Noise immunity
EN 61000-6-2:2005
Shock resistance
EN 61131-2:2004
Ambient conditions
Ambient temperature
-20 ... 70 °C (-4 ... 158 °F)
Storage temperature
-40 ... 70 °C (-40 ... 158 °F)
Cold start temperature
-40 °C (-40 °F)
Relative humidity
max. 95 %
Altitude
0 ... 2000 m
Shock and impact resistance
50 g, 11 ms, all axes
Vibration resistance
15 g at 5 - 500 Hz
Pollution degree
3
Mechanical specifications
Contact elements
PA
Degree of protection
IP65 / IP67 / IP69K
Connection
Power Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded
Material
Contacts
CuSn, gold-plated CuNi, gold-plated
Housing
Diecast zinc
Seal
FKM
Mass
500 g
Tightening torque, fastening screws
1 Nm
Tightening torque, cable gland
0.6 Nm
Dimensions
Height
200 mm
Width
59.6 mm
Length
21 mm
Construction type
Field housing
Tightening torque of clamping screws
0.5 Nm
Classifications
System
Classcode
ECLASS 13.0
27242608
ECLASS 12.0
27242608
ECLASS 11.0
27242608
ECLASS 10.0.1
27242608
ECLASS 9.0
27242608
ECLASS 8.0
27242608
ECLASS 5.1
27242608
ETIM 9.0
EC001597
ETIM 8.0
EC001597
ETIM 7.0
EC001597
ETIM 6.0
EC001597
ETIM 5.0
EC001597
UNSPSC 12.1
32151705
Details:
ICE1-8IOL-S2-G60L-V1D
Function
The module is a multiprotocol fieldbus module with 4 type A and 4 type B IOLink master ports according to IO-Link standard V1.1.
The design in fully cast metal housing is resistant to mechanical damage and due to its high degree of protection to environmental influences.
The fieldbus module serves as an interface between the controller of a fieldbus system and the field level. Thanks to its multiprotocol capability, the fieldbus module supports the Ethernet communication protocols PROFINET and EtherNet/IP.
For applications with the highest demands on system availability, the module supports PROFINET S2 system redundancy when used in a PROFINET network. The module can thus simultaneously establish an application relationship (AR) to two PROFINET controllers.
An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A. The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.
The communication protocols are configured either manually via a rotary switch or automatically. Status information for each channel is displayed via LEDs as a diagnostic function. An integrated web server enables access to the fieldbus module. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured.