Your technical, product, or application questions answered in one business day* by our team of experts.
! Please fill in all fields before submitting your question. Pepperl+Fuchs values your privacy. Please read our privacy policy.
* Pepperl+Fuchs makes every effort to provide an answer that is helpful and relevant to you. Your question is typically answered in one business day. Occasionally, an answer is delayed. In these cases, we are often researching your question, conferring with colleagues, or may route your question to another Pepperl+Fuchs location. You will be notified via e-mail regarding the status of your question.
Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Datasheet excerpt: Technical data of
VIM62PP-E1V16-0PE-I420V15
Product Description
Vibration sensor with analog current output, increased temperature resistance, suitable up to Zone 1/21 with type of protection intrinsic safety
General specifications
Type
Vibration sensor
Measuring technology
MEMS
Series
Performance Plus Line
Measured variable
Vibration velocity
Measuring range
Vibration velocity
0 ... 16 mm/s
Measurement accuracy
± 0.1 mm/s (calibration point: 90% of the measuring range; 159.2 Hz) Complies with the tolerance requirements of DIN ISO 2954 for measuring range greater than 8 mm/s
Cross-sensitivity
< 5 % of the partial lateral acceleration, which acts exactly 90° to the measuring axis
Frequency range
10 ... 1000 Hz
Averaging time
for v-rms: 2 s
Electrical specifications
Fusing
external fuse is required: 3 A , semi-time-lag , 30 V DC
Operating voltage
10 ... 30 V DC
Current consumption
max. 25 mA
Power consumption
max. 750 mW
Time delay before availability
10 s (rms filter is calculated intially with measurement data before they are available at the output)
Surge protection
up to 2 kV
Output 1
Output type
analog output, current output of the vibration variable
Output current
4 ... 20 mA
Load resistor
≤ 500 Ω
Standard conformity
Degree of protection
DIN EN 60529, IP66, IP67
Shock resistance
DIN EN 60068-2-27, 60 g, 6 ms
Vibration resistance
DIN EN 60068-2-6, 16.5 g, 10 ... 1000 Hz
Vibration evaluation
DIN ISO 10816/20816
Approvals and certificates
IECEx approval
Equipment protection level Gb
IECEx CSAE 22.0042X
Equipment protection level Db
IECEx CSAE 22.0042X
ATEX approval
Equipment protection level Gb
CSANe 21 ATEX 1074 X
Equipment protection level Db
CSANe 21 ATEX 1074 X
UL approval
Ordinary Location
E468231 cULus Listed, Class III Power Source and limited energy , if UL marking is marked on the product. For use in NFPA 70 Applications only. adapters providing field wiring on request
Maximum permissible ambient temperature
max. 60 °C (max. 140 °F)
Ambient conditions
Ambient temperature
-40 ... 60 °C (-40 ... 140 °F)
Measuring head temperature
-40 ... 125 °C (-40 ... 257 °F) directly at the mounting point
Storage temperature
-40 ... 60 °C (-40 ... 140 °F)
Mechanical specifications
Connection type
plug
Housing material
Stainless steel 1.4305 / AISI 303
Degree of protection
IP66 / IP67 only in connected state
Connector
Threading
M12
Number of pins
5
Mass
approx. 200 g
Dimensions
Length
82.35 mm
Diameter
31 mm
General information
Use in the hazardous area
see instruction manuals Only use accessories specified by the manufacturer.
Classifications
System
Classcode
ECLASS 13.0
27271103
ECLASS 12.0
27201406
ECLASS 11.0
27201406
ECLASS 10.0.1
27201406
ECLASS 9.0
27201406
ECLASS 8.0
27201406
ECLASS 5.1
27201406
ETIM 9.0
EC004309
ETIM 8.0
EC004309
ETIM 7.0
EC002959
ETIM 6.0
EC002959
ETIM 5.0
EC001758
UNSPSC 12.1
41114624
Details:
VIM62PP-E1V16-0PE-I420V15
Function
The vibration sensor determines the vibration quantity using rms (root meas square) averaging. This form of quadratic averaging or pre-filtering enables precise trend statements about the condition of the application.
The sensor’s design is impressively robust against tough environmental conditions.
The stainless steel housing provides optimal protection against corrosion. The wide temperature range of the sensor enables reliable measured values even in harsh conditions.
The simple mounting allows for commissioning in any application.
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA, Terminals with test points, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, HART communication, Test sockets, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 35 V DC, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter, Field device [3]: current sourcepa