Serviceline Industrial Sensors
Phone: 330-486-0001
Fax: 330-405-4710
Serviceline Explosion Protection
Phone: 330-486-0002
Fax: 330-963-5827

Level Radar LCR10

LCR10
  • Device for level measurement in liquids
  • Radar measuring device with Bluetooth® wireless technology
  • Measuring range up to 12 m in fluids
  • Process temperature up to 60 °C (140 °F)
  • Process pressure up to 3 bar (43 psi)
  • Accuracy up to ± 5 mm
  • Commissioning, operation and maintenance via P+F Level app

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  LCR10

General specifications
Measuring methodThe device is a measuring system that functions according to the time-of-flight method. The distance from the reference point (process connection of the measuring device) to the product surface is measured.
Construction typecompact device
SeriesLCR
Supply
Rated voltage10.5 ... 30 V DC
Current consumptioninput current : max. 25 mA
start-up current : max. 3.6 mA
Power consumptioninput power : max. 675 mW
Electrical specifications
Surge protectionintegrated
Start-up timefirst stable measured value after 20 s at 24 V DC
Interface
Interface typeBluetooth
Detection rangemax. 25 m
Configurationcommissioning, operation and maintenance via P+F Level app
- can be activated/deactivated
- password encryption
Communicationencrypted
Input
Measured variabledistance between reference point and product surface
Measuring range- device with 40 mm (1.5 inch) antenna: max. 8 m (26 foot)
- device with 40 mm (1.5 inch) antenna and flooding protection tube (accessory):
max. 12 m (39 foot)
Operating frequencyapprox. 26 GHz , K-Band
Transmitter radiated powermean power density in the direction of the beam
- at a distance of 1 m (3.3 foot): < 12 nW/cm2
- at a distance of 5 m (16 foot): < 0.4 nW/cm2
Output
Output signal4 ... 20 mA , measured value output and power supply
Signal on alarmcurrent output: 22.5 mA (in accordance with NAMUR recommendation NE 43)
P+F Level (app)
- status signal (as per NAMUR Recommendation NE 107)
- plain text display with remedial action
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529:2001
Vibration resistanceDIN EN 60068-2-64 / IEC 60068-2-64
Climate classDIN EN 60068-2-38/IEC 68-2-38
BluetoothIEEE 802.15.1
Measurement accuracy
Accuracyup to ± 5 mm
Operating conditions
Process conditions
Process temperature-40 ... 60 °C (-40 ... 140 °F)
Process pressurerelative pressure : -1 ... 3 bar (-14.5 ... 43.5 psi)
absolute pressure : < 4 bar (58 psi)
State of aggregationliquid
Dielectric constant4 ... 10 , e. g. concentrated acid, organic solvents, ester, aniline, alcohol, acetone, ...
> 10 , e.g. conductive liquids, aqueous solutions, diluted acids and bases
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Vibration resistance20 ... 2000 Hz, 1 (m/s2)2/Hz
Mechanical specifications
Degree of protectionIP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep)
IP66, NEMA 4X
Connectioncable 2 x 0,75 mm2
Materialsensor housing: PVDF
seal: EPDM
back side process connection: PVDF
cable gland: PA
conduit adapter: CuZn nickel-plated
O-ring: EPDM
counter nut: PA6.6
design ring: PBT-PC
front side process connection: PVDF
cable: PVC
Cable
Length10 m
Massapprox. 3 kg
Dimensions∅75 x 140 mm
Length140 mm
Diameter75 mm
Process connectionBack side: thread ISO228 G1, ASME MNPT1
Front side: thread ISO228 G1-1/2, ASME MNPT1-1/2
Certificates and approvals
Telecommunicationsradio license FCC
General information
Supplementary documentationtechnical information (TI)
manuals, brief instructions (BA, KA)
Accessories
Designationsee technical information (TI)

Classifications

SystemClasscode
ECLASS 13.027200513
ECLASS 12.027200513
ECLASS 11.027200513
ECLASS 10.0.127200513
ECLASS 9.027200513
ECLASS 8.027200513
ECLASS 5.127200513
ETIM 9.0EC002995
ETIM 8.0EC002995
ETIM 7.0EC002995
ETIM 6.0EC002995
ETIM 5.0EC001447
UNSPSC 12.141111950

Details: LCR10

Function

The device is suitable level measurement for liquids in storage tanks, open basins, pump shafts and canal systems.

The device is a radar measuring device with Bluetooth ® wireless technology.

Due to the wireless remote access, the device can be used in places difficult to reach and in hazardous areas.

The device can be configured and operated via the free iOS/Android app P+F Level.

The device has a PVDF housing, which guarantees a long lifetime.

The hermetically sealed wiring and fully potted electronics prevent water ingress and allow use under harsh ambient conditions.

Product Documentation: LCR10

Language Selection:
Product informationLanguageFile TypeFile Size
TI01266O Technical information LCR10ENGPDF2726 KB
Brief Instructions
KA01247O, Brief instructions LCR10ENGPDF3282 KB
Manuals
BA01577O, Manual LCR10ENGPDF3889 KB

Approvals: LCR10

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Canada Radio Approval7037A-2KLALLPDF1256 KB
Canada Radio Approval7037A-2KTALLPDF1256 KB
USA FCC ApprovalIRELCR2XKTALLPDF183 KB
USA FCC ApprovalIRELCR2XKLALLPDF186 KB
USA FCC ApprovalIRELCR2XKLALLPDF183 KB
USA FCC ApprovalIRELCR2XKTALLPDF183 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4999ALLPDF84 KB
Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.