Tuotekuvaus |
---|
Com Unit for MODBUS RTU |
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 1.8 W | |
Power consumption | 1.8 W | |
Fieldbus connection | ||
Fieldbus type | MODBUS RTU | |
MODBUS RTU | ||
Connection | wired to Ex e terminals via backplane | |
Baud rate | max. 38.4 kBit/s | |
Number of stations per bus line | max. 245 (MODBUS), max. 119 (service bus) | |
Number of channels per station | max. 80 analog, max. 184 digital (standard configuration) | |
Number of stations per bus segment | max. 31 (RS-485 standard) | |
Number of repeaters between Master and Slave | max. 3 | |
Supported I/O modules | all FB remote I/O modules | |
Bus length | max. 1200 m (FOL, 38.4 kBd), max. 1200 m (copper cable, 38.4 kBd) |
|
FOL (fiber optic link) | additional hardware required | |
Addressing | via configuration software | |
MODBUS address | standard compliant (factory standard setting: 126) |
|
Service bus address | max. 119 , redundancy address = base + 128 (automatic) | |
HART communication | via service bus | |
Redundancy | system dependent | |
Internal bus | ||
Connection | backplane bus | |
Redundancy | via front connector | |
Indicators/settings | ||
LED indication | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no Modbus RTU connection LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Environmental test | EN 60068-2-14 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Damaging gas | EN 60068-2-42 | |
Relative humidity | EN 60068-2-78 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
|
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | via backplane | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | Presafe 19 ATEX 14058U | |
Marking | Ex db eb q [ib] IIC Gb | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-1:2014 EN 60079-5:2015 EN 60079-7:2015+A1:2018 EN 60079-11:2012 |
|
International approvals | ||
ATEX approval | Presafe 19 ATEX 14058U | |
IECEx approval | IECEx PRE 19.0013U | |
Approved for | Ex db eb q [ib] IIC Gb |
|
General information | ||
System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210121 |
ECLASS 12.0 | 27210121 |
ECLASS 11.0 | 27210121 |
ECLASS 10.0.1 | 27210121 |
ECLASS 9.0 | 27210121 |
ECLASS 8.0 | 27210121 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
The MODBUS RTU com unit forms the interface between the I/O modules on the backplane and the process control system.
It supports all single width and dual width I/O modules. Thereby signals from NAMUR sensors, mechanical contacts, high-power solenoid drivers, power relays, sounders, and alarm LEDs are transported to the higher-level bus system.
The com unit can be easily configured via DTM and supports redundancy as well as HART.
Literature | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Application Report - Communication Redundancy for Uninterrupted Operation | ENG | 529 KB | |
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field Devices | ENG | 208 KB | |
Application Report - Space Saving Extension for Existing Plants | ENG | 300 KB | |
Application Report - Using Remote I/O Systems for the Efficient Digitalization of Plants | ENG | 371 KB |
System Descriptions | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Supported I/O modules | ENG | 31 KB | |
Brief Instructions | |||
Brief Instructions - Firmware update | ENG | 5602 KB | |
Safety and Security Documentation | |||
Käyttöohje | FIN | 171 KB | |
Manuals | |||
Manual for LB8107*/FB8207*, LB8111*/FB8211* com unit for MODBUS RTU/TCP | ENG | 6849 KB | |
Hardware Manual FB-Remote-I/O-System | ENG | 9157 KB | |
Software Information | |||
Software Product Note Remote I/O DTM / Softwareproduktschein Remote I/O DTM | ALL | 256 KB |
CAD | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 7022 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
EPLAN macro EDZ / EPLAN Makro EDZ | ALL | EDZ | 1267 KB |
Certificates | Sertifikaatin nro | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 19.0480 U | ALL | 1258 KB | |
China SITIIAS CCC Ex Certificate | 2021322310004115 (Mannheim) | ALL | 2333 KB | |
Europe Presafe DNV GL II 2(1)G I (M1) ATEX II (1) D | Presafe 19 ATEX 14058U | ALL | 607 KB | |
Presafe DNV GL IECEx Certificate of Conformity | IECEx PRE 19.0013U | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-4263DFIN | FIN | 1139 KB | |
UK Declaration of Conformity (P+F) | TDOC-6753_ENG | ENG | 1110 KB |
Firmware | Julkaisutiedot | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Firmware for Comm Units 8x07 / Firmware für Buskoppler 8x07 | 7.06 | ZIP | 1615 KB |
Firmware for Comm Units 8x07 / Firmware für Buskoppler 8x07 | 7.05 | ZIP | 1606 KB |
Service-Tool / Service-Tool | 3.00.0003 | ZIP | 5185 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|