G10 ultra compact module 2 inputs, 2 outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | V3.0 | |
UL File Number | E223772 "For use in NFPA 79 Applications only" | |
MTBF | 379 a | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload |
|
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
|
Electrical specifications | ||
Rated operating voltage | 18.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 40 mA (without inputs/outputs) / max. 200 mA | |
Protection class | III | |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 2 inputs for mechanical contacts | |
Supply | from AS-Interface | |
Voltage | ≤ Ue | |
Input current | ≤ 8 mA (limited internally) | |
Switching point | ||
0 (unattenuated) | ≤ 0.5 mA | |
1 (attenuated) | ≥ 2 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Output | ||
Number/Type | 2 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from AS-Interface | |
Voltage | ≥ (Ue - 9.0 V) | |
Current loading capacity | ≤ 150 mA Total current , overload and short-circuit protected | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Emitted interference | EN 61000-6-4:2011 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005 , EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.A.7 | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 7 | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
|
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
|
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
P3 | not used | |
Approvals and certificates | ||
UL approval | cULus Listed, Type 1 enclosure | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
|
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Mechanical specifications | ||
Degree of protection | housing: IP67 IP67 / IP68 / IP69K with flat cable VAZ-FK-S-* M12 socket: IP67/IP68/IP69K |
|
Connection | AS-Interface: AS-Interface flat cable In-/outputs & matching connector: M12 connector, 5-pin, A-coded, acc. to IEC 61076-2-101:2012 |
|
Material | ||
Contacts | CuSn / Au | |
Housing | PBT PC | |
Body | PUR, black | |
Cable | PUR | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Cable | ||
Sheath diameter | ∅4.8 mm | |
Color | black | |
Cores | 5 x 0.34 mm2 | |
Length | 1 m | |
Mass | 84 g | |
Tightening torque, fastening screws | 1.65 Nm | |
Tightening torque, cable gland | 0.4 Nm | |
Dimensions | ||
Height | 21.5 mm | |
Width | 27.7 mm | |
Length | 40.5 mm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
The AS-Interface G10 ultra-compact module is suitable for the remote connection of mech. switches and actuators within very limited space. The one-piece enclosure has the protection degree IP68/IP69K.
The AS-Interface flat cable is contacted via pointy, gold-plated contact pins. The exact location of the pins on the lead is ensured by the swivel mechanism.
Mech. switches and actuators are connected to the module via M12 sockets. Multiple LEDs indicate the current status of the AS-Interface strand and are used for diagnosis
Brief Instructions | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 185 KB |
Certificates | Sertifikaatin nro | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|---|
Worldwide AS-International Association AS-Interface | 133701 | ALL | 118 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-3851A | ALL | 115 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.