Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Lataa koko tietolomake PDF-tiedostona:
Tuotekuvaus |
---|
Ethernet-APL field junction box enclosure solution, brushed stainless steel with intrinsically safe spur ports |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Ethernet-APL rail field switch ARS1*-B2-I**-** , For technical data on installed electronic component see datasheets. | |
Fieldbus support | PROFIBUS PA (optional) | |
Conformity | ||
Degree of protection | EN 60529 | |
Impact resistance | EN 60079-0 | |
Ambient conditions | ||
Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation |
|
Impact resistance | 7J | |
Mechanical specifications | ||
Enclosure cover | Hinged door with captive retaining screws | |
Degree of protection | IP66 | |
Cable entry | cable gland and stopping plug options see separate table | |
Material | ||
Housing | Stainless steel 1.4404 / AISI 316L | |
Surface | brushed | |
Seal | Silicone, fire-resistant, one piece, foamed | |
Material thickness | enclosure body, enclosure cover, mounting plate: 1.5 mm | |
Dimensions | (W x H x D) 600 x 600 x 260 mm |
|
Mounting | thru-holes Ø 7 mm | |
Grounding | grounding bolt M6 , brass, nickel-plated | |
Data for application in connection with hazardous areas | ||
Certificate | PTB 17 ATEX 1011 X | |
Marking | II 3(1) G Ex ic [ia Ga] IIC T4 Gc II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135°C Dc |
|
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-1:2014+AC:2018 , EN IEC 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-18:2015+Cor.2018 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 X , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 X , Zone 2 , suitable Junction Box on request |
|
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
This field junction box is a certified enclosure solution for the Ethernet-APL rail field switch.
Depending on the switch electronics selected, devices can be located in any explosion hazardous area. The number of outputs can be selected.
Brushed stainless steel provides high corrosion and shock resistance at a wide temperature range. The integrated drain channel prevents standing water from damaging the one-piece seal.
Cable entries can be selected individually from a range of cable glands and stopping plugs. A breather drain is included by default. Tag plate, fiber optic splice, wiring terminals, surge protection and grounding bars can be custom-configured.
This field junction box is available pre-wired with all accessories and certified for explosion hazardous areas, enabling fast delivery, site installation, and commissioning.
Literature | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB | |
Application Report - First Steps Towards the Digitalization of a Recycling Plant | ENG | 376 KB | |
Application report - Improve device status visibility and adapt to the future with Ethernet-APL | ENG | 223 KB |
RSS Info Service for PANOS Updates
Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.