Yhteydenotto, Koneautomaatio
+358 20 7861 290
Yhteydenotto, Prosessiautomaatio
+358 20 7861 291

Segment Protector R-SP-E12

FieldConnex® Fieldbus
R-SP-E12
  • 12 increased safety outputs (Ex e)
  • Short circuit current limitation per output
  • Segment Protector in Zone 1/Div. 2
  • Instruments in Zone 1/Div. 1
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • High power on trunk and spurs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Lataa koko tietolomake PDF-tiedostona:


Ote tietolomakkeesta: Tekniset tiedot  R-SP-E12

Tuotekuvaus
Segment protector, junction box for fieldbus with short-circuit protection, Field junction box, module for DIN rail mounting
General specifications
Design / MountingCabinet installation
Installation in hazardous areaZone 1 / Div. 2
Fieldbus connection
Power dissipation250 mW
Main cable (Trunk)
Cable entry typescrew terminal , fixed
Rated voltage9 ... 32 V DC
Outputs
Number of outputs12
Cable entry typescrew terminal , fixed
Rated voltagemax. 32 V
Rated currentmax. 40 mA
Short-circuit currentmax. 52 mA
Self current consumptionmax. 9 mA
Voltage drop main cable/outputsmax. 1.3 V
Terminating resistorselectable 100 Ω integrated
Surge protectiontrunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED PWRgreen: Fieldbus voltage > 10 V
LED CHANNEL ERRORred flashing: short-circuit
LED COMyellow: bus activity
LED TERM ONyellow: termination activated
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance5 g , 10 ... 150 Hz
Mechanical specifications
Connection typescrew terminal , fixed
Core cross sectionmax. 2.5 mm2 / AWG 12-24
Housing materialPolycarbonate
Degree of protectionIP20
Mass800 g
Dimensions
Height100 mm
Width216 mm
Depth50 mm
MountingDIN rail mounting
Coatingresin filled
Data for application in connection with hazardous areas
EU-type examination certificatePTB 04 ATEX 2100 X
MarkingEx-Hexagon II 2 G Ex eb mb IIC T4 Gb
Maximum values
Rated voltage≤ 35 V
Prospective short-circuit current100 A
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN 60079-18:2015+A1:2017
International approvals
IECEx approvalIECEx PTB 05.0010X
Approved forEx eb mb IIC T4 Gb
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: R-SP-E12

Function

The R SP E12 Segment Protector is a device coupler that connects field instruments to the segment.

Flameproof (Ex d) field devices are connected to the trunk line via one output each. Trunk and spurs are certified increased safety (Ex e).

Short-circuit protection ensures proper operation of the segment in case of unwanted faults at the spur. Work on devices always requires a hot work permit. The integrated fieldbus terminator features high-availability design and is selectable.

Connectors are fixed screw terminals. Any grounding and shielding concept is possible based on FieldConnex enclosure solutions.

Customizable housings host one or more Segment Protectors for different output counts.

Informative Literature: R-SP-E12

Language Selection:
LiteratureKieliTiedostotyyppiTiedoston koko
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: R-SP-E12

Language Selection:
Safety and Security DocumentationKieliTiedostotyyppiTiedoston koko
KäyttöohjeFINPDF216 KB

Approvals: R-SP-E12

Language Selection:
CertificatesSertifikaatin nroKieliTiedostotyyppiTiedoston koko
Brasil TUV Rheinland Brazil Ex eTÜV 13.1153 XALLPDF1179 KB
China SITIIAS CCC Ex Certificate2021322310003756 (Singapore)ALLPDF831 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe PTB ATEX Category 2 GPTB 04 ATEX 2100XALLPDF374 KB
PTB IECEx Certificate of ConformityIECEx PTB 05.0010XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0207EFINFINPDF1133 KB

Liitännäistuotteet: R-SP-E12

Matching System Components
Connection of Ex d certified devices, Glass fiber reinforced polyester, impact resistant, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: Zone 1 - high-power trunk, Instrument location / spur protection: Zone 1 - increased safety, Function: Device coupler, Design / Mounting: Outside installationpa
Segment Protector Junction Box, Brushed Stainless Steel, Connection of Ex d certified devices, Brushed enclosure, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: Zone 1 - high-power trunk, Instrument location / spur protection: Zone 1 - increased safety, Function: Device coupler, Design / Mounting: Outside installationpa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …