Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Lataa koko tietolomake PDF-tiedostona:
Tuotekuvaus |
---|
Ethernet IO module with 8 digital inputs/outputs |
General specifications | ||
---|---|---|
UL File Number | E223772 | |
Indicators/operating means | ||
LED indication | see manual | |
Rotary switch | Setting the fieldbus protocol | |
Electrical specifications | ||
Rated operating voltage | 18 ... 30 V | |
Nominal voltage | 24 V DC | |
Current consumption | 120 mA | |
Current loading capacity | Max. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 9 A per module |
|
Galvanic isolation | between US and UL | |
Interface 1 | ||
Interface type | Industrial Ethernet | |
Physical | M12, D-coded | |
Protocol | PROFINET IO with media redundancy protocol (MRP) EtherNet/IP with Device Level Ring (DLR) EtherCAT® |
|
Transfer rate | 10/100 Mbps | |
Inputs/Outputs | ||
Number/Type | 8 digital inputs (X1 – X4), 8 digital outputs (X5 – X8) Inputs: 2-, 3-, 4-wire PNP, DC, supply from US Outputs: 2-, 3-, 4-wire, PNP, DC, supply from UL Short-circuit protected |
|
Sensor supply | max. 200 mA per port (X1 – X4) via US | |
Output current | max. 2 A per channel / 4 A per port (X5 – X8) via UL | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Emitted interference | EN 61000-6-4:2007+A1:2011 | |
Noise immunity | EN 61000-6-2:2005 | |
Shock resistance | EN 61131-2:2004 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Cold start temperature | -40 °C (-40 °F) | |
Relative humidity | max. 95 % | |
Altitude | 0 ... 2000 m | |
Shock and impact resistance | 50 g, 11 ms, all axes | |
Vibration resistance | 15 g at 5 - 500 Hz | |
Pollution degree | 3 | |
Mechanical specifications | ||
Contact elements | PA | |
Degree of protection | IP65 / IP67 / IP69K | |
Connection | Power Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded |
|
Material | ||
Contacts | CuSn, gold-plated CuNi, gold-plated |
|
Housing | Diecast zinc | |
Seal | FKM | |
Mass | 500 g | |
Tightening torque, fastening screws | 1 Nm | |
Tightening torque, cable gland | 0.6 Nm | |
Dimensions | ||
Height | 200 mm | |
Width | 59.6 mm | |
Length | 21 mm | |
Construction type | Field housing | |
Tightening torque of clamping screws | 0.5 Nm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The ICE1-8DI8DO-G60L-V1D is a multiprotocol fieldbus module with 8 digital inputs and 8 digital outputs.
The G60L design in fully cast metal housing is resistant to mechanical damage and environmental influences. The G60L has protection class IP65/IP67.
The fieldbus module serves as an interface between the controller of a fieldbus system and the field level. Thanks to its multiprotocol capability, the fieldbus module supports the Ethernet communication protocols PROFINET, EtherNet/IP, and EtherCAT.
An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A. The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.
The communication protocols are configured either manually via a rotary switch or automatically. The diagnostics display status information for each channel via LEDs. An integrated web server enables access to the fieldbus module. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured.
Literature | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Application Report - Industrial Communication - IO-Link Master - CNC Machines | ENG | 757 KB | |
Product Information - Ethernet IO Modules with IO-Link Master | ENG | 499 KB |
Safety and Security Documentation | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
Safety Datasheet / Sicherheitsdatenblatt | ALL | 383 KB | |
Manuals | |||
Manual ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D | ENG | 6805 KB |
CAD | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 12400 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 70 KB |
Certificates | Sertifikaatin nro | Kieli | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|---|
Canada, USA UL | CoC E223772 RptRef E223772-20170316 | ALL | 240 KB | |
ODVA Ethernet/IP | 11612.01 | ALL | 69 KB | |
Worldwide | Z11883 | ALL | 83 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-3185CFIN | FIN | 195 KB | |
UK Declaration of Conformity (P+F) | TDOC-7493_ENG | ENG | 172 KB |
Device Description Files/Drivers | Julkaisutiedot | Tiedostotyyppi | Tiedoston koko |
---|---|---|---|
EtherNet/IP EDS-Files / EtherNet/IP EDS-Dateien | 04/2019 | ZIP | 73 KB |
PROFINET GSDML-Files / PROFINET GSDML-Dateien | 03/2019 | ZIP | 66 KB |
Ethercat configuration File / Ethercat-Konfigurations-Datei | 03/2018 | ZIP | 28 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|