Sélectionnez votre pays
LB5005A Thermocouple Converter
Principaux avantages en un coup d'œil
- 4 channels
- Converter for thermocouples and mV-signals
- Installation in Zone 2 or safe area
- Simulation mode for service operations (forcing)
- Line fault detection (LFD)
- Permanently self-monitoring
- Module can be exchanged under voltage
Afficher plus




Remarque
Tous les documents relatifs aux produits, tels que les certificats, les déclarations de conformité, etc., qui ont été émis avant la conversion sous le nom de Pepperl+Fuchs GmbH ou Pepperl+Fuchs AG, s'appliquent également à Pepperl+Fuchs SE.
DE
- DE
- EN
Fiche techniqueFonctionClassificationInformative LiteratureProduct DocumentationDesign / SimulationAgrémentsProduits associés
Données techniques relatives à LB5005A
Occupied slots | 2 |
Connection | backplane bus | |
Rated voltage | Ur | 12 V DC , only in connection with the power supplies LB9*** |
Power dissipation | 0.75 W | |
Power consumption | 0.75 W |
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit |
Compensation (reference junction CJC) | internal cold junction compensation or external cold junction |
Number of channels | 4 | |||||||
Suitable field devices | ||||||||
| ||||||||
Suitable sensors | ||||||||
| ||||||||
Connection | channel I: 1+, 2-; channel II: 5+, 6-; channel III: 9+, 10-; channel IV: 13+, 14- | |||||||
Measuring range | -65 ... 75 mV with LFD , -75 ... 75 mV without LFD | |||||||
Smallest span | 5 mV for 0.1 % accuracy | |||||||
Linearity error | 0.1 % | |||||||
Conversion time | max. 300 ms (4 channels) without LFD max. 600 ms (4-channel) with LFD | |||||||
Compensation (reference junction CJC) | internal cold junction compensation or external cold junction | |||||||
Test voltage | 1.5 kV input - input 1.5 kV input - bus and auxiliary power | |||||||
Line fault detection | can be switched on/off for each channel via configuration tool , | |||||||
|
Deviation | |||||
|
LED indication | Power LED (P) green: supply Status LED (I) red: line fault (collective alarm) , red flashing: communication error | |
Coding | optional mechanical coding via front socket |
Electromagnetic compatibility | |||||
|
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Environmental test | EN 60068-2-14 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Damaging gas | EN 60068-2-42 | |
Relative humidity | EN 60068-2-78 |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Altitude | max. 2000 m | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Degree of protection | IP20 when mounted on backplane | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 150 g | |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
Certificate | PF 08 CERT 1234 X | |||||||
| ||||||||
Galvanic isolation | ||||||||
| ||||||||
Directive conformity | ||||||||
|
IECEx approval | ||||||||
|
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |