Slots |
Occupied slots | 2 |
Supply |
Connection | backplane bus |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** |
Power dissipation | 2 W |
Power consumption | 2.5 W |
Fieldbus connection |
Fieldbus type | MODBUS TCP |
Ethernet Interface |
Connection type | wired to Ex e terminals via backplane |
Transfer rate | 10 MBit/s |
Station connection | directly to PCS or PLC or via hubs or switches |
Bus length | max. 100 m (Ethernet standard) |
Addressing | IP address assigned via Ethernet |
Ethernet address | IP V4 address (factory standard setting: 0.0.0.0, auto IP, DHCP) |
Number of channels per station | max. 80 analog, max. 184 digital |
Supported I/O modules | all FB remote I/O modules |
HART communication | via Ethernet |
Internal bus |
Connection | backplane bus |
Redundancy | via left front connector |
Service interface |
Connection | via right front connector in connection with service adapter SERV8001 |
Indicators/settings |
LED indication | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no Modbus TCP connection LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Fieldbus standard | IEEE 802.3 |
Environmental test | EN 60068-2-14 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Damaging gas | EN 60068-2-42 |
Relative humidity | EN 60068-2-78 |
Ambient conditions |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | via backplane |
Mass | approx. 750 g |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Data for application in connection with hazardous areas |
EU-type examination certificate | Presafe 19 ATEX 14058U |
| Marking | Ex db eb q [ib] IIC Gb |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-1:2014 EN 60079-5:2015 EN 60079-7:2015+A1:2018 EN 60079-11:2012 |
International approvals |
ATEX approval | Presafe 19 ATEX 14058U |
IECEx approval | IECEx PRE 19.0013U |
| Approved for | Ex db eb q [ib] IIC Gb
|
General information |
System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |